NTRODUCTION
The Cornelius "CH" Series Recirculating Water Chiller is designed to provide an accurate, reliable and user-friendly
system for cooling a continuous flow of water and keep it at a constant temperature in various closed loop or tank
cooling applications.
The "CH" Series Chiller consists of an air-cooled refrigeration system housed in a sturdy sheet metal frame and
cabinet. A standard pump and insulated water reservoir package provides a complete liquid cooling and circulating
system.
The "CH" Series Chiller is designed to operate in a clean laboratory or industrial environment where ambient
temperatures range from 40 to100° F (5 to 38° C). With proper installation, operation and maintenance, the "CH"
Series Chiller will provide years of trouble free service.
U
I
NPACKING AND
This unit was thoroughly inspected before leaving the factory and the carrier has accepted and signed for it. Any
damage or irregularities should be noted at the time of delivery and immediately reported to the carrier. Request a
written inspection report from the Claims Inspector to substantiate any necessary claims. In the event that an
immediate replacement is necessary, please contact Cornelius Chiller Sales at 1-800-551-4423.
D
D
ESIGN
ATA
The voltage and the frequency are indicated on the serial number plate, located behind the drip tray and on the right
hand side near the controls.
Cooling Capacity:
BTU/hr (W) at 80° F (27° C) and 70° F
(21° C) Liquid Temperature
Compressor Horsepower
Electrical Data:
Voltage/Phase/Hertz/Amperage
Refrigerant Type
Physical Dimensions, Width X Depth X
Height
Fittings:
Process Connections
Optimum Process Liquid Flow GPM
(Liters/Min)
Condenser Air Flow (CFM)
© 2002-2015, Cornelius Inc.

GENERAL INFORMATION

NSPECTION
3,000 (879)
.25 (.2 kW)
115/1/60
7.5 Amps
R134a
17.125" X 14.125" X 13.375"
(43.5 cm X 35.9 cm X 34 cm)
1/2" FPT (S/S)
0.6 (2.72)
225
CH Series Chiller Operator's & Installation Manual
Table 1:
CH250
3,000 (879)
.25 (.2 kW)
230/1/60
3.8 Amps
R134a
17.125" X 14.125" X 13.375"
(43.5 cm X 35.9 cm X 34 cm)
1/2" FPT (S/S)
0.6 (2.72)
225