Lighting Instructions; Burner Operation; Maintenance Instructions - Heat Wise SU-3 Manual

Gas burner 200,000 btu/h to 400,000 btu/h
Hide thumbs Also See for SU-3:
Table of Contents

Advertisement

To light the SU-3 Gas Burner
1. Set the thermostat to the lowest
temperature
2. The control knob on the gas
valve should be in the "OFF"
position for at least five minutes.
3. Rotate the control knob counter-
clockwise to the "ON" position
and set the thermostat to the
desired temperature settings
Before turning the burner on, check for gas supply leaks. Check the wiring diagrams; install
manometers before and after the gas valve. Keep the observation port of the boiler or furnace
open. Follow the instructions on the nameplate of the burner to turn it on. Follow the sequence of
operations for the control (see pages 8 and 9). Record the readings below.
BURNER OPERATION: Record the Readings at Steady State
Draft over fire at steady state (should be –0.02 "W.C. or zero)
Natural Gas CO
% = (9.0% to 9.8%) or O
2
Stack Temperature (300
Percentage of Carbon Monoxide (CO) in PPM
Incoming Gas/LP pressure = "W.C. (minimum 5")
Natural Gas manifold gas pressure = "W.C. (3.5" required + - 0.3")
Carbon Monoxide in flue ( less than 100 PPM ideal; should not exceed 400PPM)

Maintenance Instructions

Once a year, a qualified service agency needs to be contracted for other than routine maintenance.
1.
The blower motor is the only moving part. It does not require lubrication, since the ball bearings have
been permanently lubricated.
2.
The user should do periodic visual checks of the burner and the flame.
3.
Laundry lint or dog and/or cat hairs should not go inside the blower. If they are seen, they should be
removed after disconnecting the power to the burner and cover parts should be installed before starting the
burner.
4.
Keep the area around the conversion burner clear and free from combustible materials, gasoline, and
other flammable vapors and liquids.
5. No obstruction for the flow of combustion and ventilating air (ref. Page 4).

LIGHTING INSTRUCTIONS

1. Turn the thermostat off, or turn the main power off
2. Wait five minutes
3. Turn the main power on
1. Rotate the control knob on the gas valve to the
"OFF" position
2. Set the thermostat to the lowest temperature

BURNER OPERATION

% = (5.0% to 3.5%)
2
o
o
F minimum, 550
F maximum)
: TO BE FIXED/ATTACHED NEAR BURNER
Reset, if Flame Lockout Occurs
To shut the burner off