15.4 Racking the removable voltage transformers to test position

Preconditions
High-voltage door closed
Removable voltage transformers in service position
Racking tool available
Key for padlock available
The actuating opening for racking the removable voltage transformers is located on the control board of the
high-voltage door.
139-2021.9 / 07
NOTICE
Maloperation
If the removable voltage transformers are not correctly positioned in the panel,
damages may occur when the removable voltage transformers are racked.
If you hear a noise or if you notice a resistance, stop racking immediately.
Inform the regional Siemens representative.
Fig. 174: Racking tool for the removable voltage transformers
Fig. 175: Actuating opening for racking the removable voltage transformers
Operating the removable voltage transformers