Electrical Data - International comfort products N92ESN Installation Instructions Manual

Single-stage, 35-in. (889 mm) tall high efficiency condensing gas furnace
Table of Contents

Advertisement

VOLTS---
HERTZ---
FURNACE SIZE
PHASE
0401410
115--- 60--- 1
0401712
115--- 60--- 1
0601412
115--- 60--- 1
0601714
115--- 60--- 1
0801716
115--- 60--- 1
0802120
115--- 60--- 1
1002120
115--- 60--- 1
1202420
115--- 60--- 1
* Permissible limits of the voltage range at which the unit operates satisfactorily.
# Unit ampacity = 125 percent of largest operating component's full load amps plus 100 percent of all other potential operating components' (EAC, humidifier,
etc.) full load amps.
Time ---delay type is recommended.
{
Length shown is as measured one way along wire path between furnace and service panel for maximum 2 percent voltage drop.
}
38
Fig. 37 - - Example of Single Stage Furnace Control
Table 11 – Electrical Data
OPERATING VOLTAGE
MAXIMUM
RANGE*
Maximum*
Minimum*
127
104
127
104
127
104
127
104
127
104
127
104
127
104
127
104
Specifications subject to change without notice.
UNIT
UNIT
AMPACITY#
AMPS
7.1
9.8
7.1
9.8
7.2
9.9
7.2
9.9
7.2
9.9
9.6
12.9
9.7
13.0
9.7
13.0
MAXI-
MINIMUM
MUM
MAXIMUM
WIRE
WIRE
FUSE OR CKT
SIZE
LENGTH
BKR AMPS
AWG
FT (M)}
14
37 (11.5)
14
37 (11.5)
14
37 (11.4)
14
37 (11.4)
14
37 (11.4)
14
28 (8.7)
14
28 (8.7)
14
28 (8.7)
440 01 4541 00
A190022
15
15
15
15
15
15
15
15

Advertisement