Mitsubishi Electric MSZ-SF25VE-E1 Service Manual page 32

Indoor unit
Table of Contents

Advertisement

OPERATION INDICATOR
Abnormal
No.
Operation indicator lamp
point
Left lamp lights and lower lamp fl ashes.
MXZ type
Operation
1
mode
2.5-second OFF
setting
10-5. TROUBLE CRITERION OF MAIN PARTS
MSZ-SF25VE
MSZ-SF35VE
MSZ-SF25VE2 MSZ-SF35VE2
MSZ-SF25VE3 MSZ-SF35VE3
Part name
Room temperature
thermistor (RT11)
Indoor coil thermistor
(RT12, RT13)
Indoor fan motor (MF)
Vane motor (MV)
OBH600E
Symptom
Outdoor unit
operates but
indoor unit does
not operate.
MSZ-SF42VE
MSZ-SF42VE2
MSZ-SF42VE3
Check method and criterion
Measure the resistance with a tester.
Refer to 10-7. "Test point diagram and voltage", "Indoor electronic control
P.C. board", for the chart of thermistor.
Check 10-6.
"Check of indoor fan motor".
Measure the resistance between the terminals with a tester.
(Temperature: 10 - 30°C)
Color of the lead wire
RED - BLK
Condition
The operation mode of the each indoor unit
is differently set to COOL (includes DRY) and
HEAT at the same time, the operation mode
of the indoor unit that has operated at fi rst has
the priority.
MSZ-SF50VE
MSZ-SF50VE2
MSZ-SF50VE3
Normal
232 - 268 Ω
32
Remedy
• Unify the operation mode.
Refer to outdoor unit service
manual.
Figure
BLK
ROTOR
BLK
RED
BLK
BLK