38VMR072-336 Outdoor Unit for Variable Refrigerant Flow (VRF) Heat Recovery Systems Engineering Data Book Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations. Catalog No. 20-38VMR001-03 Printed in U.S.A. Form 38VMR-3ED Pg 1 08-20...
Combination Ratio Restrictions e.g. Outdoor unit 38VMA240RDS5-1(6-1) has 240 as the capacity index. It is recommended to keep a proper combination ratio for the entire system. Table 17 —Combination Ratio MAX. COMBINATION RATIO MIN. COMBINATION RATIO 40VMH *1 only When 40VMA and indoor Including 40VMH *1 or 40VMV Other indoor unit 40VMV only...
Page 19
Center Of Gravity (Cont.) 11-13/16 31-7/64 78-11/32 NOTE: All dimensions are shown in inches. Fig. 2 —38VMA144RDL, 38VMA168, 192, 216, 240RDS Models 11-13/16 105-29/32 31-7/64 NOTE: All dimensions are shown in inches. Fig. 3 —38VMA240RDL, 38VMA264, 288, 312, 336RDS Models...
DIMENSIONS 42-7/8 All dimensions are shown in inches 4-7/8 4-7/8 Anchor Bolt Holes 31-1/8 29-7/8 28-1/2 52-3/4 Bottom View Discharge Air Control Box Front Panel Intake Air Intake Air Front Panel Left View 7-3/4 7-3/4 21-3/4 Front View Gauge Port High Pressure Side Low Pressure Side Conencting pipe...
Page 21
DIMENSIONS (CONT.) All dimensions are shown in inches Bottom View Discharge air Front panel Control box Control box Intake air Intake air Front panel DETAIL C SCALE 1:3 Gauge port (Detect the pressure/ refrigerant replenishment/ Left view vacuumize) Front view High pressure side (The connected pipe diameter...
Page 22
DIMENSIONS (CONT.) All dimensions are shown in inches Fig. 6 —38VMA240RDL, 38VMA264, 288, 312, 336RDS Models Table 20 —Dimensions (in inches) MODEL ɸA ɸB 1-1/8 1-3/8 1-1/8 1-3/8 1-1/8 1-3/8 1-1/8 1-5/8 1-1/8 1-5/8...
Refrigerant Circuit Diagrams Table 21 —Refrigerant Circuit Symbol Name Major Function Refrigerant Circuit Electrical Wiring Diagram Diagram INV1 Compressor A Inverter Varies the refrigerant flow rate by adjusting the frequency based on objective INV2 Compressor B compressor pressure. INV3 Compressor C Separates oil from high pressure gas refrigerant, which is pumped out from Oil separator compressor.
Wiring Diagrams Brown Compressor Fan A drive board A Left Reactor A Black Blue Black Black CN13 Blue Black White Brown Ferrite Fan B core White Right Blue Black White CN4 CN5 CN14 Black Blue Rectifier A Black Black Black Black Ferrite core Black...
Page 28
Table 22 —Legend Table 23 —DSP1 and DSP2 Display Content CODE NAME DISPLAY MEANING XT1-XT2 Terminal Block Phase Loss Error XS1-XS2 Plug Comm. Error with MDC and Indoor Unit XP1-XP2 Jack T3 or T4 Temperature Sensor Error H-PRO 1-4 High Pressure ON/OFF Switch Voltage Protection H-YL1 High Pressure Sensor...
Page 29
Wiring Diagrams (Cont.) Brown Compressor Fan A drive board A Left Compressor Reactor A drive board A Black Blue Black Black The first fan Black Main board Black CN13 Blue Blue Blue DC fan drive board A Black White Ferrite Brown Fan B AC filter...
Page 30
Table 24 —Legend Table 25 —DSP1 and DSP2 Display Content CODE NAME DISPLAY MEANING XT1-XT2 Terminal Block Phase Loss Error XS1-XS8 Plug Comm. Error with MDC and Indoor Unit XP1-XP8 Jack T3 or T4 Temperature Sensor Error H-PRO 1-4 High Pressure ON/OFF Switch Voltage Protection 0H0/ H-YL1...
Page 31
WIRING DIAGRAMS (CONT.) Orange ’ Black Fan A White L2’ White XP1 XS1 Left White IC17 L3’ White Reactor A Blue-2 Red-2 White Black Black Blue Black Fan B White XP2 XS2 Right ’ White Black Blue-3 Rectifier A Red-3 Black Ferrite core Green...
Page 32
Fig. 13 —Legend Fig. 14 —DSP1 and DSP2 Display Content CODE NAME DISPLAY MEANING XT1-XT2 Terminal Block Phase Loss Error XS1-XS2 Plug Comm. Error with MDC and Indoor Unit XP1-XP2 Jack T3 or T4 Temperature Sensor Error H-PRO 1-4 High Pressure ON/OFF Switch Voltage Protection H-YL1 High Pressure Sensor...
Page 33
WIRING DIAGRAMS (CONT.) Orange ’ Black Left Fan A White L2’ White XP1 XS1 White IC17 L3’ White Compressor drive board A Reactor A Blue-2 Red-2 White Black Black Main board Black The first fan Blue Blue Black Blue DC fan drive board A Black AC filter...
Page 34
Fig. 16 —Legend Table 26 —DSP1 and DSP2 Display Content CODE NAME DISPLAY MEANING XT1-XT2 Terminal Block Phase Loss Error XS1-XS4 Plug Comm. Error with MDC and Indoor Unit XP1-XP4 Jack T3 or T4 Temperature Sensor Error H-PRO 1-4 High Pressure ON/OFF Switch Voltage Protection 0H0 / 20H0 H-YL1...
Field Wiring GENERAL CAUTIONS 1. Choose the correct AWG according to MCA values based on UL-1995. Follow technical standards for electrical equipment and wiring regulations. 2. When proceeding with the wiring and connections outside, avoid anything that could damage the power line and transmission cable, such as exposing to sunlight and rain.
Page 36
POWER SUPPLY Table 27 —Electrical Characteristics of Outdoor Units OUTDOOR UNITS (208/230-3-60) COMPRESSOR MODEL VOLTS VOLTAGE RANGE MCA(A) RECOMMENDED FUSE SIZE (A) SC(A) 38VMA072RDS5-1 38VMA096RDS5-1 38VMA120RDS5-1 38VMA144RDL5-1 38VMA168RDS5-1 38VMA192RDS5-1 38VMA216RDS5-1 208/230V 187 to 253V 38VMA240RDS5-1 38VMA240RDL5-1 38VMA264RDS5-1 38VMA288RDS5-1 38VMA312RDS5-1 38VMA336RDS5-1...
Page 37
CONTROL WIRING Use 2-Core stranded shielded communication wire. Wiring length limitations must be observed to avoid any communication interference. Table 29 —Wiring Length Limitation Max. length to Outdoor L1+L2,L5 ≤3937ft [1,200m] AWG 18 Max. total length to Indoor units L3, L3+L4 ≤3937ft [1,200m] AWG 18 Max.
REFRIGERANT PIPING DESIGN NOTE: For calculation purposes, assume equivalent pipe length of the branching pipe header to be 1.6 ft. (0.5m). Piping Scheme Fig. 49 —Piping Lengths and Drop Heights Table 56 — Permitted Pipe Lengths and Drop Heights DESCRIPTION ALLOWABLE VALUE (ft) PIPES Total Extension of Pipe (Liquid Pipe)
Page 53
Table 57 —Main Pipe Selection (A) OUTDOOR UNIT CAPACITY (KBTU/H) HIGH PRESSURE SIDE (in.) LOW PRESSURE SIDE 1-1/8 1-1/8 1-1/8 1-1/8 1-1/8 1-1/8 1-1/8 1-3/8 240L 1-1/8 1-3/8 1-1/8 1-3/8 1-1/8 1-3/8 1-1/8 1-5/8 1-1/8 1-5/8 Table 58 —Grouped Indoor Unit Pipe Selection (B) TOTAL DOWN-STREAM IDU CAPACITY LIQUID PIPE GAS PIPE...
Page 54
Table 61 —Twinned Port Indoor Unit Pipe Selection (g,h,i,j) LIQUID SIDE (in.) GAS SIDE (in.) INDOOR UNIT CAPACITY Y-JOINT MODEL 40VM900043 Table 62 —Y-Joint Selection TOTAL CAPACITY Y-JOINT DOWNSTREAM INDOOR HIGH PRESSURE SIDE (in.) LOW PRESSURE SIDE (in.) LOW PRESSURE SIDE (in.) MODEL UNITS (KBTU/H) <...
Connected Capacity Ratio Table 63 —Indoor Unit Combination Total Capacity Index INDOOR UNIT COMBINATION RATIO (KBTU/H) OUTDOOR UNIT TON (KBTU/H) 135% 120% 110% 100% 6 (72) 97.2 86.4 79.2 72.0 64.8 57.6 50.4 43.2 36.0 8 (96) 129.6 115.2 105.6 96.0 86.4 76.8...
Page 57
38VMA***RD system can extend the piping flexibly within its limitation to suit the actual situation. However, it will cause a decrease in cooling/heating capacity due to pressure loss because of the longer piping length. Use the following correction factor to calculate the capacity (approximately). Table 65 —Cooling Capacity Correction 38VMA072RDS5-1(RDS6-1) 38VMA096RDS5-1(RDS6-1) 38VMA120RDS5-1(RDS6-1) 38VMA144RDL5-1(RDL6-1)
Page 60
38VMA240RDL5-1(RDL6-1) 38VMA264RDS5-1(RDS6-1) 38VMA288RDS5-1(RDS6-1) 38VMA312RDS5-1(RDS6-1) 38VMA336RDS5-1(RDS6-1) How to Get the Equivalent Piping Length Bends cause pressure loss when refrigerant is transported, so make sure there are as few bends in the system as possible. Piping length needs to include the actual length and the equivalent length where the bends are counted. 38VMA072~336RDS(L)5-1 38VMA072~336RDS(L)6-1 Equivalent length = (Actual piping length to the farthest indoor unit) + (1.64 x number of bends on the piping) [ft.]...
Page 62
Table 71 —Refrigerant to Add for Sub MDC SUB MDC MODEL NAME CHARGE AMOUNT PER UNIT (lbs) 40VMD006S 40VMD008S 40VMD010S 40VMD016S Table 72 —Refrigerant to Add for Connected Capacity TOTAL CONNECTED CAPACITY of INDOOR UNITS CHARGE AMOUNT PER UNIT (lbs) 50%~100% 100%~120% 120%~130%...
Page 63
MAXIMUM REFRIGERANT CHARGE There is a limit to the amount of refrigerant that can be charged into a unit regardless of the amount yielded by the formula. Observe the maximum refrigerant charge in the “Maximum Refrigerant Charge” in the table below. Table 73 —Maximum Refrigerant Charge Outdoor Unit Model Name Max *1 Refrigerant Charge...
Page 64
Fig. 55 —Temperature Operation Limits – Heating Table 74 —Operating Temperature Range MODE OUTDOOR TEMPERATURE INDOOR TEMPERATURE Cooling 5~125 F°DB (-15~51.7 C°DB) 59~75 F°WB (15~23.9 C°WB) Heating -13~64 F°WB (-25~17.8 C°WB) 54~86 F°DB (12.2~30 C°DB) Cooling Main 23~75 F°DB (-5~23.9 C°DB) 59~75 F°WB (15~23.9 C°WB) Heating Main 21~64 F°WB (-6.1~17.8 C°WB)
OUTDOOR USE UTILISATION À L’EXTÉRIEUR UTILISATION À L’EXTÉRIEUR SERIAL NO. SERIAL NO. 1016V00001 1016V00001 Carrier Corporation Carrier Corporation Fig. 61 —38VMA144RDL5-1 Fig. 62 —38VMA168RDS5-1 CONFORMS TO UL STD 1995 CONFORMS TO UL STD 1995 CERTIFIED TO CSA STD. CERTIFIED TO CSA STD.
Page 172
OUTDOOR USE UTILISATION À L’EXTÉRIEUR UTILISATION À L’EXTÉRIEUR SERIAL NO. SERIAL NO. 1016V00001 1016V10001 Carrier Corporation Carrier Corporation Fig. 66 —38VMA144RDS6-1 Fig. 65 —38VMA240RDS5-1 CONFORMS TO UL STD 1995 CONFORMS TO UL STD 1995 CERTIFIED TO CSA STD. CERTIFIED TO CSA STD.
Page 173
320 PSIG PRESSURE 320 PSIG Short-circuit current:5kA rms symmetrical,460V maximum Short-circuit current:5kA rms symmetrical,460V maximum OUTDOOR USE OUTDOOR USE UTILISATION À L’EXTÉRIEUR UTILISATION À L’EXTÉRIEUR SERIAL NO. SERIAL NO. 1016V10001 1016V10001 Carrier Corporation Carrier Corporation Fig. 69 —38VMA216RDS6-1 Fig. 70 —38VMA240RDS6-1...
Short-circuit current:5kA rms symmetrical,230V maximum OUTDOOR USE OUTDOOR USE UTILISATION À L’EXTÉRIEUR UTILISATION À L’EXTÉRIEUR SERIAL NO. SERIAL NO. Carrier Corporation Carrier Corporation Fig. 71 —38VMA240RDL5-1 Fig. 72 —38VMA264RDS5-1 CONFORMS TO UL STD 1995 CONFORMS TO UL STD 1995 CERTIFIED TO CSA STD.
Page 175
Short-circuit current:5kA rms symmetrical,460V maximum OUTDOOR USE OUTDOOR USE UTILISATION À L’EXTÉRIEUR UTILISATION À L’EXTÉRIEUR SERIAL NO. SERIAL NO. Carrier Corporation Carrier Corporation Fig. 76 —38VMA240RDS6-1 Fig. 75 —38VMA336RDS5-1 CONFORMS TO UL STD 1995 CONFORMS TO UL STD 1995 CERTIFIED TO CSA STD.