Carrier 38AUD Installation, Start-Up And Service Instructions Manual page 21

Air cooled condensing units 50 hz with puron (r-410a) refrigerant sizes 07-14
Table of Contents

Advertisement

UNIT
V ---Ph---Hz
38AUZ*07
400--- 3--- 50
38AUZ*08
400--- 3--- 50
NOTE: See "Legend and Notes for Tables 11 & 12"
UNIT
V--- Ph--- Hz
38AUD*12
400--- 3--- 50
38AUD*14
400--- 3--- 50
NOTE: See "Legend and Notes for Tables 11 & 12"
Legend and Notes for Tables 11 and 12
LEGEND:
FLA
---
Full Load Amps
LRA
---
Locked Rotor Amps
MCA
---
Minimum Circuit Amps
Protection
NEC
---
National Electrical Code
RLA
---
Rated Load Amps
}
Units are suitable for use on electrical systems where voltage
supplied to the unit terminals is not below or above the listed
limits.
NOTES:
1. The MCA and Fuse values are calculated in accordance with
The NEC. Article 440.
2. Motor RLA and LRA values are established in accordance
with Underwriters' Laboratories (UL). Standard 1995.
3. Unbalanced 3-Phase Supply Voltage
Never operate a motor where a phase imbalance in supply
voltage is greater than 2%. Use the following formula to de-
termine the percentage of voltage imbalance.
Table 11 – Electrical Data — 38AUZ*07- - 14 50 Hz Units
VOLTAGE
COMPRESSOR 1
RANGE
}
MIN
MAX
RLA
360
440
9.7
360
440
12.2
Table 12 – Electrical Data — 38AUD*12- - 14 50 Hz Units
VOLTAGE
COMPRESSOR
RANGE
}
1
MIN
MAX
RLA
LRA
360
440
7.8
52
360
440
10.6
74
OFM
LRA
OTY
FLA
64
2
.07
100
2
.07
COMPRESSOR
OFM (ea)
2
RLA
LRA
QTY
FLA
7.8
52
2
10.6
74
2
Example: Supply voltage is 400-3-50
% Voltage Imbalance
= 100 x
AB = 394 v
BC = 401 v
AC = 396 v
(394 + 401 + 396)
Average Voltage =
=
Determine maximum deviation from average voltage.
(AB) 397 – 394 = 3 v
(BC) 401 – 397 = 4 v
(AC) 397 – 396 = 1 v
Maximum deviation is 4 v.
Determine percent of voltage imbalance.
% Voltage Imbalance
This amount of phase imbalance is satisfactory as it is below the
maximum allowable 2%.
IMPORTANT: If the supply voltage phase imbalance is more than
2%, contact your local electric utility company immediately.
21
POWER
DISCONNECT
SUPPLY
SIZE
MCA
Fuse
FLA
13.5
20
13
16.7
25
16
POWER
DISCONNECT
SUPPLY
MCA
Fuse
FLA
0.7
19.0
25
20
0.7
25.3
30
26
max voltage deviation from average voltage
average voltage
1191
=
3
397
4
= 100 x
397
= 1.00%
LRA
68
104
SIZE
LRA
108
152
3

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

38auz

Table of Contents