Table 4. Gas heater operating data
Heating Input Rate
—Btu/h
Minimum Supply Gas Pressure Natural/LP
Manifold Gas Pressure
(a)
Combustion Blower Suction Pressure (1
Combustion Blower Suction Pressure (2
Minimum Flame Sensing Current
Normal Sensing Current Range
Flue Gas Temperature Rise Above Ambient
Flue Gas Content - % CO
2
Minimum Supply Air Temperature Across Heat Exchanger
(a)
Staged gas heat units have a positive pressure gas valve. Never adjust the staged gas pressure valve to a negative pressure.
(b)
A voltage reading across pens (V+) and (V-) is equatable to the flame sensing current. One volt equals one micro amp.
Table 5. Piping
Length of Pipe (ft)
15
30
45
60
75
Note: Capacity of Pipe of Different Diameters and Lengths in Cu. Ft. Per Hr. with Pressure Drop of 0.3" and Specific Gravity of 0.60.
Table 6. Specific gravity multipliers
Specific Gravity
Figure 20. Schematic diagram for field gas piping to units
1/8" NPT Test Plug
Gas Supply Line
Gas shuttoff (Field Supplied
outside unit cabinet.)
24
st
Stage)
nd
Stage)
(b)
1/2" Pipe
3/4" Pipe
76
176
52
120
43
99
38
86
77
155
0.50
0.55
0.60
0.65
Field supplied ground
Union
Drip Leg
125,000
180,000
4.5/11.0
4.5/11.0
3.5
-1.3 to -1.7
-1.3 to -1.7
-1.3 to -1.7
-1.3 to -1.7
8.0 to 16 Micro Amps DC
7.0% to 8.0% (Natural Gas)
7.5% to 9.0% (Propane)
Iron Pipe Size (IPS) Inches
1" Pipe
345
241
199
173
345
6" MIN
To Gas Train
Unit Access Hole
225,000
4.5/11.0
3.9
3.6
-1.1 to -1.5
-1.1 to -1.5
5.0 Micro Amps DC
230 to 300 F
40° F
1¼" Pipe
1½" Pipe
750
535
435
380
545
Multipliers
1.10
1.04
1.00
0.96
250,000
4.5/11.0
3.5
-1.1 to -1.5
-1.1 to -1.5
1220
850
700
610