Step 9 - Install External Condensate Trap And Line - Bryant 548J***D Series Installation Instructions Manual

Single package rooftop heat pump sizes 17 and 24 with puronr (r--410a) refrigerant
Hide thumbs Also See for 548J***D Series:
Table of Contents

Advertisement

Hood Top
Shipping
Position
Fig. 13 - - Hood Top – Shipping Position
Hood
Package
Fig. 14 - - Hood Package – Shipping Location
To remove the hood parts package:
1. Remove the back blower access panel.
2. Locate and cut the strap, being careful to not damage
any wiring.
3. Carefully lift the hood package carton through the
back blower access opening.
See Fig. 15 for identification of the various parts of the
hood assembly.
Apply Seal Strip
to the front of
this flange
Apply Seal Strips
to the back of
these flanges
2
5
6
Seal Strips
Item #
Fig. 15 - - Hood Part Identification and Seal Strip
Application Areas
To assemble the outside air hood:
1. Remove hood top panel from shipping position on
unit end.
Apply Seal Strips
3
to the back of
Apply Seal Strip
these surfaces
to the front of
this flange
7
7
4
4
4
4
Apply Seal Strip
to the back of
1
this flange
Description
Qty
1
Angles
4
2
Side Plates
2
3
Hood
1
4
Outdoor Air Screens
4
5
Side Filter Supports
2
6
Side Drip Angles
2
7
Top Diverters
2
2. Install four angles to the upper end panel using the
screws provided
3. Apply seal strip to mating flanges on the side plates
of the hood (see Fig. 15).
4. Secure side plates to panel using the screws provided.
5. Apply seal strip to mating flange of the hood (see
Fig. 15).
6. Secure top flange using screws provided in kit.
7. Install outdoor air screens by sliding them into the
channel formed by the four angles installed in step 2.
C09134
Make sure that the screens extend across the entire
length of the hood.
8. Install side filter supports using the screws provided
9. Install side drip angles using the screws provided.
10. Run a continuous length of seal strip across the hood
covering the engagement holes in the lower hood.
11. Install top diverter using the screws provided.
12. On units with barometric relief, remove screws at bot-
tom of relief damper. Do not discard damper door.
C13785
Fig. 16 - - Hood Assembly – Completed
Step 9 — Install External Condensate Trap and
Line
The unit has one
the end of the condensate pan (see Fig. 17) See Fig. 2 (or
Fig. 3), item "E", in the view labeled "BACK" for the
location of the condensate drain connection.
2
5
6
STANDARD
SIDE DRAIN
Fig. 17 - - Condensate Drain Pan Connection
C09079
The piping for the condensate drain and external trap can
be completed after the unit is in place. Hand tighten
fittings to the drain pan fitting. Provide adequate support
for the drain line. Failure to do so can result in damage to
the drain pan. See Fig. 18.
17
3
/
-in. condensate drain connection on
4
C09090
C09056