Dc-Link Voltage Under/Over Error (Error Code : E466) - Samsung AM036TXMDCH Service Manual

System air conditioner
Hide thumbs Also See for AM036TXMDCH:
Table of Contents

Advertisement

1) Check the power and restarting after power reset
2) Check the power cable connection, and joint cable connection
3) Check the reactor and reactor wire
4) Check the fuse on the EMI PBA
5) Check the Terminal block, power terminal cabinet and the power wire assembly
Turn off the power
Is the power cable connected properly?
Check the reactor and
reactor wire connection
1. Is wire connection between the reactor
outdoor unit inverter PBA normal?
2. Is there any problem on reactor coil?
(such as scratch/pressed/
broken terminal/loose
terminal)
Cont.
Samsung Electronics
Yes
Yes
No
Re-connect the power cable
[Common: Power joint connection failure]
1. Correctly connect the wire between the reactor
outdoor unit inverter PBA
No
normal operation
2. Change the reactor
End service
[AM
XMDC
✳✳✳✳
Check for
End service
Check for normal operation
series]
55