Magnetising Inrush Detector (81Hbl); Figure 3-6 Magnetising Inrush Detector - Siemens 7SR21 Manual

Overcurrent relay
Hide thumbs Also See for 7SR21:
Table of Contents

Advertisement

3.6

Magnetising Inrush Detector (81HBL)

Voltage Inputs:
Current Inputs:
Disable:
Map Pickup LED:
Logical operation of the harmonic blocking can be tested by current injection at 100Hz to cause operation of the
blocking signals.
©2010 Siemens Protection Devices Limited
7SR21 & 7SR22 Argus Commissioning and Maintenance

Figure 3-6 Magnetising Inrush Detector