Commissioning The Boiler - Baxi 100/2 HE Plus Installation & Servicing Instructions Manual

Wall mounted powered flue condensing boiler, gas fired central heating unit
Table of Contents

Advertisement

Reset
Fig. 35
DO NOT check gas pressure here
Inlet Gas Pressure Test Point
28
High
Low
Control Knob
ON
Fig. 36
10.0
10.1
1. Reference should be made to BS 5449 Section 5
when commissioning the boiler.
2. Flush the whole system using a suitable flushing agent
(see Section 6.2) and vent the radiators. Check for
water leaks.
3. Refill the system with inhibitor following the inhibitor
manufacturer's instructions and BS 7593 Code of
Practice for Treatment of Water in Domestic Hot
Water Central Heating Systems (see Section 6.2).
4. Complete the label supplied with the inhibitor and
attach to the inside of the boiler case. Detail of system
treatment should be added for future reference.
5. Turn the gas supply on and purge according to in GB
Gas Service
BS 6891 and in IE I.S. 813 "Domestic Gas Installations".
Cock
6. Remove the top RH securing screw and hinge down
the PCB housing to gain access to the gas service cock
(see Fig. 32). Turn the gas service cock anticlockwise to
the ON position and check for gas soundness up to the
gas valve (Fig. 34).
7. Turn the boiler control knob fully clockwise to
'HIGH' (Fig. 35) and run the system and check the
boiler for correct operation.
Open
Fig. 34
NOTE: The boiler is self-regulating and the gas
rate will modulate between inputs of 33.76kW and
10.3kW dependent upon the system load. The
input is factory set at 24.90kW and can be altered
to 33.76kW - see section 8.8. No adjustment of
the gas valve is permissible.
8. With the system cold and all controls calling for heat
check the gas pressure at the inlet tapping of the gas
valve (Fig. 36). The pressure must be a minimum of
18.1 mbar (Working Pressure). Check that the gas rate
is no greater than 3.3m
WARNING: The PCB Control and Fan
Assembly is 325 Vdc. Isolate at supply
before access.

Commissioning the Boiler

Commissioning the Boiler
3
/h.