Refrigerant Piping - Toshiba rav-sm1103at-e Installation Manual

Split type
Hide thumbs Also See for rav-sm1103at-e:
Table of Contents

Advertisement

GOOD
Absorb vibration
with vibration-proof
Fixing leg
rubber pads
Foundation
GOOD
Bottom plate of
outdoor unit
Foundation
Support the bottom surface of
the fixing leg that is in contact
with and underneath the bottom
plate of the outdoor unit.
NO GOOD
If only the
Do not support
end of the
the outdoor unit
fixing leg is
only with the
supported, it
may deform.
Foundation
Set the out margin of the anchor bolt to 15 mm or less.
15 or less
When water is to be drained through the drain hose,
attach the following drain nipple and waterproof
rubber cap, and use the drain hose (Inner diam:
16 mm) sold on the market. Also seal knockout hole
and the screws securely with silicone material, etc.,
to prevent water from leaking.
Some conditions may cause dewing or dripping of
water.
EN-17
When collectively draining discharged water
completely, use a drain pan.
Waterproof rubber cap
Drain nipple
Knockout hole
Waterproof
rubber cap
Drain nipple
For Reference
If a heating operation is to be continuously performed for
a long time under the condition that the outdoor
temperature is 0 °C or lower, draining defrosted water
fixing leg.
may be difficult due to the bottom plate freezing,
resulting in trouble with the cabinet or fan.
It is recommended to procure an anti-freeze heater
locally in order to safely install the air conditioner.
For details, contact the dealer.
- 9 -
5

REFRIGERANT PIPING

Knockout of Pipe Cover
Knockout procedure
Open
Front direction
Down direction
• The indoor/outdoor connecting pipes can be
connected in 4 directions.
Take off the knockout part of the pipe cover through
which pipes or wires will pass through the base plate.
• Detach the pipe cover and tap on the knockout section
a few times with the shank of a screwdriver. A
knockout hole can easily be punched.
• After punching out the knockout hole, remove burrs
from the hole and then install the supplied protective
bush and guard material around the passage hole to
protect wires and pipes.
Be sure to attach the pipe covers after pipes have
been connected. Cut the slits under the pipe covers to
facilitate the installation.
After connecting the pipes, be sure to mount the pipe
cover. The pipe cover is easily mounted by cutting off
the slit at the lower part of the pipe cover.
* Be sure to wear heavy work gloves while working.
How to remove the front panel
1.
Remove the screws from the front panel.
2.
Pull the front panel downward.
Removing the front panel, the electric parts are located
in front.
• The metal pipes are attachable to the piping holes. If
the size of the conduit pipe being used does not match
the hole, adjust the hole size to match the pipe size.
Rear direction
Pipe cover
Side direction
Cord clamp
Electric parts box
Service panel
Pipe valve
fixing plate
Wiring
hole
EN-18