Gas Pressure Setting - Rinnai REU-VR2632FFUD - 26i Installation And Use Manual

Continuous flow water heater
Table of Contents

Advertisement

The working gas pressure on the water heater is electronically controlled and factory set. Under normal
circumstances it does not require adjustment during installation. The pressure should be checked
when the unit is installed and each time it is serviced to ensure that it is correct.
Contact Rinnai before attempting to alter the gas pressure if you are unsure of what to do.
Incorrect adjustment can void the warranty.
1. Turn 'OFF' the gas supply.
2. Turn 'OFF' 230V power supply.
3. Remove the front cover from the appliance.
4. Check gas type switches no.1 and no.2 of Dip SW2 are in the correct position for the type of gas
used. See Fig. 1
5. Attach pressure gauge to burner test point. (Fig. 2)
Burner
test point
32 liters
6. Turn 'ON' the gas supply.
7. Turn 'ON' 230V power supply.
8. If remote controllers are fitted, turn the unit 'ON' at the controller and select a maximum delivery
temperature.
9. Open a hot water tap fully. (CAUTION: Ensure building occupants do not have access to hot
water outlets during this procedure.) Wait for the unit to light.
* Simply changing the position of the dip switches will not convert the
unit from one gas type to the other. The conversion procedure requires
a change of injector manifold. Contact Rinnai or your supplier.
NOTE

GAS PRESSURE SETTING

Dip SW1(8P)
Dip SW2(6P)
Dip SW2
34
26 liters