Owner’s Manual Liquid-cooled, Prepackaged Standby Generators Model Number: ASPAS1BBL015 Not intended for use in critical life support applications. ONLY QUALIFIED ELECTRICIANS OR CONTRACTORS SHOULD ATTEMPT INSTALLATION!! DEADLY EXHAUST FUMES. OUTDOOR INSTALLATION ONLY! This manual should remain with the unit.
Proper maintenance and care of the generator ensure a minimum number of problems and keep operating expenses at a minimum. See a Bryant Dealer for serv- ice aids and accessories. Operating instructions presented in this manual assume that the standby electric system has been installed by a Bryant Dealer or other competent, qualified contractor.
If using a procedure, work method or operating technique that Bryant does not specifically recommend, ensure that it is safe for others. Also make sure the procedure, work method or operating technique utilized does not render the generator unsafe.
FIRE or EXPLOSION may result. Keep the area surrounding the generator clean and free from debris. • Bryant generator sets may operate using one of several types of fuels. All fuel types are potentially FLAMMABLE and/or EXPLOSIVE and should be handled with care.
• Protect the switch at all times against excessive moisture, dust, dirt, lint, construction grit and cor- rosive vapors. • Failure to utilize a Bryant transfer switch with this generator will void the warranty. Model Rating...
(Figure 1.3). Figure 1.3 - Engine Protective Devices Section 1 - General Information Bryant Liquid-cooled 15 kW Generators 1.7.1 LOW OIL PRESSURE SWITCH This switch is normally-closed (N.C.), but is held open by engine oil pressure during engine running.
The unit will not start or crank if the fuse is blown. Replace the fuse with one of the same size, type, and rating. Bryant normally uses an AGC fuse rated at 15 amps (part number 022676). Handle shipping cartons and crates with care. Use care to avoid damage from dropping, bumping, colli- sion, etc.
14 inches of water column (0.4 to 0.5 psi) at all load ranges. Section 1 — General Information Bryant Liquid-cooled 15 kW Generators 1.12 RECONFIGURING THE FUEL (1.5 liters) All models are configured for natural gas from the factory.
Section 2 — Installation Bryant Liquid-cooled 15 kW Generators 1.14 ENGINE OIL RECOMMENDATIONS The unit has been filled with 15W-40 engine oil at the factory. Use a high-quality detergent oil classified “For Service SJ or latest available.” Detergent oils keep the engine cleaner and reduce carbon deposits.
Notice that both the STANDBY and the UTILITY power supplies to the transfer switch are protected against overload by a main line circuit breaker. Figure 2.1 – Basic Standby Electric System Bryant recommends the use of a Bryant transfer switch in conjunction with this generator. Bryant...
Section 2 — Installation Bryant Liquid-cooled 15 kW Generators EMERGENCY CIRCUIT ISOLATION METHOD This prevents overloading the generator by keeping electrical loads below the wattage/amperage capacity of the generator. If the generator is powering only crit- ical loads, within the wattage/amperage capacity, dur- ing utility power outages, consider using the emer- gency circuit isolation method.
Section 2 — Installation Bryant Liquid-cooled 15 kW Generators • Spilled electrolyte is to be washed down with an acid-neutralizing agent. A common practice is to use a solution of one pound (500 grams) bicarbon- ate of soda to one gallon (4 liters) of water.
Section 3 — Operation Bryant Liquid-cooled 15 kW Generators Before starting the generator for the first time, the installer must complete the following procedures. For follow-up maintenance information and/or service intervals, please refer to Section 4, “Maintenance.” 2.11.2 TRANSFER SWITCH...
• Set the generator main circuit breaker to its ON or CLOSED position. Bryant Liquid-cooled 15 kW Generators The generator will start and exercise once every seven days. During this weekly exercise, the unit runs for about 20 minutes and shuts down. Transfer of loads •...
Section 4 — Maintenance Bryant Liquid-cooled 15 kW Generators MAINTENANCE PERFORMED BY AUTHORIZED SERVICE FACILITIES A. EVERY THREE MONTHS 1.Check battery state of charge and condition. 2.Inspect and test fuel system. 3.Check transfer switch. 4.Inspect exhaust system. 5.Check engine ignition system.
Look for fuel, oil or coolant leaks. Section 4 — Maintenance Bryant Liquid-cooled 15 kW Generators 4.5.7 INSPECT EXHAUST SYSTEM Inspect the exhaust system at least once every three months. Check all exhaust system pipes, mufflers, clamps, etc.
Section 4 — Maintenance Bryant Liquid-cooled 15 kW Generators Figure 4.2 - Oil Filter After refilling the crankcase with oil, always check oil level on dipstick. NEVER OPERATE ENGINE WITH OIL BELOW THE DIPSTICK “ADD” MARK. 7. Start engine and check for oil leaks.
Page 19
3. Have the state of charge and condition checked. This should be done with an automotive-type bat- tery hydrometer. Section 4 — Maintenance Bryant Liquid-cooled 15 kW Generators DANGER Storage batteries give off explosive hydrogen gas. This gas can form an explosive mixture around the battery for several hours after charging.
Section 4 — Maintenance Bryant Liquid-cooled 15 kW Generators SCHEDULED MAINTENANCE The following is a recommended maintenance schedule for small standby and residential generator sets. The established intervals in the schedule are the maximum recommended when the unit is used in an average service application.
Page 21
Correct as necessary. 12. Test the engine and transfer switch safety devices. Correct and/or adjust as necessary. Section 4 — Maintenance Bryant Liquid-cooled 15 kW Generators Level 2 Task Required Task Comp. to be done Comp.
Page 22
Section 4 — Maintenance Bryant Liquid-cooled 15 kW Generators Maintenance Level 1 Tasks Recom- mended to be done monthly/ 10 hrs. 13. Initiate an automatic start and transfer of the unit to site load and exercise it for at least 1 hour looking for...
Under normal operating conditions, if repair of generator set or replacement of any parts is necessary dur- ing the warranty period, you must contact a dealer. Failure to have the repair or replacement performed by a Bryant dealer will result in non-coverage of warranty repair cost. Section 5 — Troubleshooting...
Section 8 - Electrical Data Bryant Liquid-cooled 15 kW Generators Wiring Diagram — Control Panel —Drawing No. 0F5243 24 Bryant BLACK BLACK BLACK...
Page 27
Section 8 - Electrical Data Bryant Liquid-cooled 15 kW Generators Electrical Schematic — Control Panel —Drawing No. 0F5244 BLACK BLACK BLUE BLUE Bryant 25...
Page 28
Section 8 - Electrical Data Bryant Liquid-cooled 15 kW Generators Wiring Diagram — 1.5L Engine — Drawing No. 0E0343-B CONTROL PANEL CONNECTION LEGEND CC - CONTROL CONTACTOR DIS - DISTRIBUTOR DCA - DC ALTERNATOR FS - FUEL SOLENOID GRD - GROUND...
Page 29
Electrical Schematic — 1.5L Engine — Drawing No. 0A7182-C ACTUATOR CONNECTOR Section 8 - Electrical Data Bryant Liquid-cooled 15 kW Generators DC-A 12V BATTERY BLACK LEGEND CC - CONTROL CONTACTOR DCA - DC ALTERNATOR FS - FUEL SOLENOID GRD - GROUND...
Generac. The ECS Warranty applies only to the emission control system of your new engine. If there is any conflict in terms between the ECS Warranty and the Bryant Warranty, the ECS Warranty shall apply except in circumstances where the Generac Warranty may provide a longer warranty period.
*Generac engine types covered by this warranty statement include the following: 1) Prepackaged Standby Generator 2) Auxiliary Power Unit (APU) Generator 3) Standby Generator Part 2 Bryant Liquid-cooled 15 kW Generators EMISSION CONTROL SYSTEM WARRANTY 3) Ignition System including: a) Spark plug b) Ignition module...
Page 48
"PREPACKAGED EMERGENCY AUTOMATIC STANDBY GENERATORS" For a period of two years from the date of original sale, Bryant warrants that its generator will be free from defects in material and workmanship for the items and period set forth below. Bryant will, at its option, repair or replace any part which, upon examination, inspection and testing by a Bryant Dealer, is found to be defective.