About the 4232CBM

The 4232CBM Connected Building Module is intended
to provide connection between compatible Honeywell
control panels and supported third-party software and
hardware products. It provides an interface between
the control panel's ECP bus and external equipment
with either RS422 or RS232 interfaces. The connection
and configuration of this device is application-specific.
Please refer to the documentation for your external
equipment for information on which connection method
to use, and how to configure the external device to
communicate properly with the 4232CBM.
NOTE: The connected building features offered by the
4232CBM are not evaluated by ETL or UL.
Compatible Controls
Control
VISTA-15P, VISTA-15PSIA
VISTA-20P, VISTA-20PSIA
VISTA-21iP, VISTA-21iPSIA V3.13 or higher
VISTA-128BPT,
VISTA-128BPTSIA
The 4232CBM module connects to the control panel
via the panel's ECP terminals, and connects to the
external computer or other equipment via either RS422
or RS232 connections, according to the application.
The module is powered via the control panel's ECP
+12VDC connection.
Wiring the Module
Refer to the diagram below for connections.
1. 4232CBM to External Equipment Connection: For RS232 applications, connect the three RS232 lines
(GND, Tx and Rx) to the external equipment. For RS422 applications, connect the four RS422 lines (Tx+/-
and Rx +/-) to the appropriate points on the external equipment.
LED INDICATORS
DATA (RECEIVING)
(MESSAGE WAITING)
PANEL (KEYPAD DATA)
CONTROL PANEL
ECP CONNECTION
CONTROL
4232CBM
DATA OUT
RX (YELLOW)
DATA IN
TX (GREEN)
GND
GND (BLACK)
12VDC
12VDC (RED)
NOTES:
A. The connections shown above are used for most applications where the external equipment has a male DE-9
connector (for example, PCs and most home automation equipment).
B. For RS422 applications, refer to the documentation for your external equipment.

INSTALLATION AND SETUP GUIDE

Firmware Level
V9.1 or higher
All versions
4232CBM PC BOARD
POWER
4-WIRE
HARNESS
Connected Building Module

Mounting the Module

Mount the module inside the control panel cabinet
using double-sided tape (supplied). Make sure the
solder connections on the bottom of the PC board do
not touch the cabinet.

LED Indications

Four green LEDs indicate the following conditions:
LED
Condition
external
On
device
Flashing
Panel
On or Blink
Power
Slow Blink
Flashing
Off
Data
Blink
Specifications
Board Dimensions
Current Drain
ECP Input Voltage
Wire Run Length
Temperature
120
RESISTOR
NOTE: IF WIRE RUN TO RS422 DEVICE EXCEEDS 100 FT, INSTALL
120 OHM RESISTOR BETWEEN RX
THE 4232CBM.
RS422
CONNECTIONS
TX
TX
RX
RS232
RX
CONNECTIONS
TX
RX
GND
NOT USED
4232CBM
Meaning
message waiting for the
external device
check connection to the
external device
keypad data waiting for the
external device
power on, normal operation
power on, not configured
power off
receiving data from the external
device
3.75" W x 2.5" L x 0.875" D
50mA nominal; 75mA max
8-14VDC
RS232 Connection: 50 ft max with
24 AWG twisted pair wire
RS422 Connection: 1000 ft max
with 24 AWG twisted pair wire
ECP Connection: 900 ft max home
run with 22 AWG unshielded wire
32°F (0°C) to 140°F (60°C)
AND RX
TERMINALS ON
STANDARD
9-PIN
SERIAL
CONNECTOR
9-PIN
CONN.
2(RX)
3(TX)
5(GND)
4232CBM-001-V0
Continued on Other Side

Advertisement

loading

Summary of Contents for Honeywell 4232CBM

  • Page 1 Temperature 32°F (0°C) to 140°F (60°C) 1. 4232CBM to External Equipment Connection: For RS232 applications, connect the three RS232 lines (GND, Tx and Rx) to the external equipment. For RS422 applications, connect the four RS422 lines (Tx+/- and Rx +/-) to the appropriate points on the external equipment.
  • Page 2 2. 4232CBM to Control Panel Connection: Plug the connector of the 4-wire harness (supplied) into the 4-pin ECP connector on the 4232CBM board. Connect the flying leads to the appropriate control panel ECP terminals as shown below. ZONE 1 CONNECT...