Bryant DURAPAC PLUS SERIES 542J Installation, Start-Up And Service Instructions Manual

Single package rooftop heat pump units durapac plus series sizes 150,180 12 and 15 tons

Advertisement

Quick Links

CONTENTS
SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . . . . . . . . 1
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-18
I. Step 1 - Provide Unit Support. . . . . . . . . . . . . . . . . 1
II. Step 2 - Rig and Place Unit . . . . . . . . . . . . . . . . . . . 1
III. Step 3 - Field Fabricate Ductwork . . . . . . . . . . . . . 1
V. Step 5 - Trap Condensate Drain . . . . . . . . . . . . . . . 3
VIII. Step 8 - Install Outdoor-Air Hood. . . . . . . . . . . . . 10
IX. Step 9 - Install All Accessories . . . . . . . . . . . . . . 10
XI. Step 11 - Defrost Cycle . . . . . . . . . . . . . . . . . . . . . 18
START-UP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .18-22
SERVICE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .23-29
TROUBLESHOOTING. . . . . . . . . . . . . . . . . . . . . . . . . . . .30-35
INDEX . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
START-UP CHECKLIST . . . . . . . . . . . . . . . . . . . . . . . . . . CL-1

SAFETY CONSIDERATIONS

Installation and servicing of air-conditioning equipment can
be hazardous due to system pressure and electrical compo-
nents. Only trained and qualified service personnel should
install, repair, or service air-conditioning equipment.
Untrained personnel can perform basic maintenance func-
tions of cleaning coils and filters and replacing filters. All
other operations should be performed by trained service per-
sonnel. When working on air-conditioning equipment, observe
precautions in the literature, tags and labels attached to the
unit, and other safety precautions that may apply.
Follow all safety codes. Wear safety glasses and work gloves.
Use quenching cloth for unbrazing operations. Have fire
extinguisher available for all brazing operations.
WARNING: Before performing service or mainte-
nance operations on unit, turn off main power switch to
unit. Electrical shock could cause personal injury.

INSTALLATION

IMPORTANT: Units have high ambient operating limits. If
limits are exceeded, the unit will automatically lock the com-
pressor out of operation. Manual reset will be required to
restart the compressor.
I. STEP 1 - PROVIDE UNIT SUPPORT
A. Roof Curb
Assemble and install accessory roof curb in accordance with
instructions shipped with the curb. Accessory roof curb and
information required to field fabricate a roof curb are shown
installation, start-up and
service instructions
SINGLE PACKAGE ROOFTOP
HEAT PUMP UNITS
Dura Pac Plus Series
Cancels: II 542J-150-3
in Fig. 1 and 2. Install insulation, cant strips, roofing, and
counter flashing as shown. Ductwork can be secured to roof
Page
curb before unit is set in place. Horizontal adapter installa-
tion is shown in Fig. 2.
IMPORTANT: The gasketing of the unit to the roof curb is crit-
ical for watertight seal. Install gasket supplied with the roof
curb as shown in Fig. 1. Improperly applied gasket can result
in air leaks and poor unit performance.
Curb should be level. This is necessary to permit unit drain to
function properly. Unit leveling tolerances is ±
ear ft in any direction. Refer to Accessory Roof Curb Installa-
tion Instructions for additional information as required.
B. Alternate Unit Support
When the curb cannot be used, support unit with sleepers
using unit curb support area. If sleepers cannot be used, sup-
port long sides of unit with a minimum of 3 equally spaced
4-in. x 4-in. pads on each side.
II. STEP 2 - RIG AND PLACE UNIT
Inspect unit for transportation damage. File any claim with
transportation agency. Keep unit upright, and do not drop.
Use spreader bars over unit to prevent sling or cable damage.
Rollers may be used to move unit across a roof. Level by using
unit frame as a reference; leveling tolerance is ±
linear ft in any direction. See Fig. 1 for additional leveling tol-
erance information. Unit weight is shown in Table 1.
Four lifting holes are provided in ends of unit base rails as
shown in Fig. 3. Refer to rigging instructions on unit.
A. Positioning
Provide clearance around and above unit for airflow, safety,
and service access (Fig. 4 and 5).
Do not install unit in an indoor location. Do not locate air
inlets near exhaust vents or other sources of contaminated air.
Although unit is weatherproof, guard against water from
higher level runoff and overhangs.
B. Roof Mount
Check building codes for weight distribution requirements.
III. STEP 3 - FIELD FABRICATE DUCTWORK
Secure all ducts to building structure. Use flexible duct con-
nectors between unit and ducts as required. Insulate and
weatherproof all external ductwork, joints, and roof openings
with counter flashing and mastic in accordance with applica-
ble codes.
Ducts passing through an unconditioned space must be insu-
lated and covered with a vapor barrier.
The 542J units with electric heat require a 1-in. clearance for
the first 24 in. of ductwork.
542J
Sizes 150,180
12 and 15 Tons
II 542J-150-4
3/15/06
1
/
in. per lin-
16
1
/
in. per
16

Advertisement

Table of Contents
loading

Summary of Contents for Bryant DURAPAC PLUS SERIES 542J

  • Page 1: Table Of Contents

    SINGLE PACKAGE ROOFTOP HEAT PUMP UNITS CONTENTS SAFETY CONSIDERATIONS ......1 INSTALLATION .
  • Page 2 — —...
  • Page 3: Step 4 - Make Unit Duct Connections

    NOTE: CRRFCURB013A00 is a fully factory preassembled horizontal adapter and includes an insulated transition duct. The pressure drop through the adapter curb is negligible. For horizontal return applications: The power exhaust and barometric relief dampers must be installed in the return air duct. Fig.
  • Page 4 UNIT SIZE 542J NOMINAL CAPACITY (tons) OPERATING WT (lb) Al/Al* Al/Al Coated* Unit Al/Cu* Cu/Cu* Electric Heat EconoMi$erIV Roof Curb† COMPRESSOR Type (Number) Cylinders Oil Change (oz.) (each circuit) REFRIGERANT TYPE Charge (lb) System 1 System 2 OUTDOOR COIL Rows Fins/in.
  • Page 5 NOTES: Fig. 4 — Base Unit Dimensions — 542J150 — — 1. Refer to print for roof curb accessory dimensions. 2. Dimensions in ( ) are in millimeters. Center of Gravity. Direction of airflow. 5. Ductwork to be attached to accessory roof curb only.
  • Page 6 Fig. 5 — Base Unit Dimensions — 542J180 — — NOTES: 1. Refer to print for roof curb accessory dimensions. 2. Dimensions in ( ) are in millimeters. Center of Gravity. Direction of airflow. 5. Ductwork to be attached to accessory roof curb only.
  • Page 7: Step 6 - Make Electrical Connections

    NOTE: Do not drill in this area, as damage to basepan may result in water leak. Fig. 6 — Air Distribution — Thru-the-Bottom (542J180 Shown) NOTE: Do not drill in this area, as damage to basepan may result in water leak. Fig.
  • Page 8 Install a Bryant-approved accessory thermostat assembly according to the installation instructions included with the accessory. Refer to unit Price Pages or contact your local Bryant representative for more information. Locate thermostat assembly on a solid wall in the conditioned space to sense average temperature.
  • Page 9 COMPRESSOR VOLTAGE VOLTAGE RANGE UNIT No. 1 (3 Ph, 542J 60 Hz) Min Max RLA LRA RLA LRA 208/230 39.7 19.9 208/230 28.2 14.1 LEGEND — Full Load Amps HACR — Heating, Air Conditioning and Refrigeration — Locked Rotor Amps —...
  • Page 10: Step 7 - Make Outdoor-Air Inlet Adjustments

    VII. STEP 7 — MAKE OUTDOOR-AIR INLET ADJUSTMENTS A. Manual Outdoor-Air Damper All units (except those equipped with a factory-installed EconoMi$erIV) have a manual outdoor-air damper to provide ventilation air. Damper can be preset to admit up to 25% out- door air into return-air compartment.
  • Page 11: Step 10 - Adjust Factory-Installed Options

    A. Motormaster® I Control Installation Install Field-Fabricated Wind Baffles Wind baffles must be field-fabricated for all units to ensure proper cooling cycle operation at low ambient temperatures. See Fig. 18 for baffle details. Use 20-gage, galvanized sheet metal, or similar corrosion-resistant metal for baffles. Use field-supplied screws to attach baffles to unit.
  • Page 12 OUTDOOR AIR TEMPERATURE SENSOR FRAME (INSTALLED OPERATION ECONOMI$ERIV SCREWS SCREWS POSITION) Fig. 20 — EconoMi$erIV Component Locations — End View Potentiometer Default Settings: LEGEND Power Exhaust DCV — Demand Controlled Ventilation Minimum Pos. IAQ — Indoor Air Quality DCV Max. LALS —...
  • Page 13 B. EconoMi$erIV Standard Sensors Outdoor Air Temperature (OAT) Sensor The outdoor air temperature sensor (HH57AC074) is a 10 to 20 mA device used to measure the outdoor-air temperature. The outdoor-air temperature is used to determine when the EconoMi$erIV can be used for free cooling. The sensor must be field-relocated.
  • Page 14 Fig. 23 — EconoMi$erIV Controller Potentiometer and LED Locations LED ON LED ON LED OFF LED ON LED OFF LED OFF DEGREES FAHRENHEIT Fig. 24 — Outside Air Temperature Changeover Set Points RETURN AIR TEMPERATURE SENSOR OR ENTHALPY SENSOR Fig. 25 — Return Air Temperature or Enthalpy Sensor Mounting Location Outdoor Enthalpy Changeover For enthalpy control, accessory enthalpy sensor (part num-...
  • Page 15 CONTROL CONTROL POINT CURVE APPROX. °F (°C) AT 50% RH 73 (23) 70 (21) 67 (19) 63 (17) (13) (10) (10) (13) APPROXIMATE DRY BULB TEMPERATURE— °F (°C) Fig. 26 — Enthalpy Changeover Settings 24 Vac Open Free Cool Fig. 27 — EconoMi$erIV Controller (29) (32) (35)
  • Page 16 Minimum Position Control There is a minimum damper position potentiometer on the EconoMi$erIV controller. See Fig. 23. The minimum damper position maintains the minimum airflow into the building during the occupied period. When using demand ventilation, the minimum damper posi- tion represents the minimum ventilation position for VOC (volatile organic compound) ventilation requirements.
  • Page 17 See Table 8. Use setting 1 or 2 for Bryant equipment. See Table 8. 1. Press Clear and Mode buttons. Hold at least 5 sec- onds until the sensor enters the Edit mode.
  • Page 18: Xi. Step 11 — Defrost Cycle

    XI. STEP 11 — DEFROST CYCLE The defrost timer is factory set at 30 minutes. The timer may be field-adjusted to 50 or 90 minutes by moving the wire from the 30 minute contact to the 50 to 90 minute contact. At the end of the time period, the defrost cycle will begin.
  • Page 19 AIRFLOW (Cfm) Watts 3750 0.55 4000 0.70 4250 0.86 4500 1.04 4750 1084 1.23 5000 1267 1.44 5250 1464 1.67 1011 5500 1675 1.91 1041 5750 1901 2.17 1072 6000 1020 2142 2.44 1103 6250 1055 2398 2.73 1135 AIRFLOW (Cfm) Watts 3750...
  • Page 20 AIRFLOW (Cfm) Watts 4500 4800 5100 5400 1118 5700 1284 6000 1458 6300 1644 6600 1856 6900 2078 7200 2316 7500 2584 AIRFLOW (Cfm) Watts 4500 1070 2113 4800 1078 2269 5100 1086 2439 5400 1097 2626 5700 1110 2835 6000 1122 3053...
  • Page 21 UNIT SIZE ACCESSORY/FIOP 542J Electric Heaters EconoMi$erIV Glycol Coil LEGEND FIOP — Factory-Installed Option *Do not operate unit with electric heat at this cfm. Operation at this cfm is below electric heat required minimum cfm. †Do not operate unit at this cfm. Operation at this cfm is above unit maximum cfm limit.
  • Page 22 VII. OUTDOOR FANS AND MOTORS Fans and motors are factory set. Refer to Outdoor-Fan Adjustment section on page 24 as required. VIII. RETURN-AIR FILTERS Check that correct filters are installed in filter tracks. See Table 1. Do not operate unit without return-air filters. IX.
  • Page 23: Service

    SERVICE WARNING: Before performing service or mainte- nance operations on unit, turn off main power switch to unit. Turn off accessory heater power switch if applicable. Electrical shock could cause personal injury. I. CLEANING Inspect unit interior at beginning of each heating and cool- ing season and as operating conditions require.
  • Page 24 Fig. 35 — 542J150 Indoor-Fan Motor Section IV. INDOOR FAN, 542J180 UNITS A. Performance Adjustment Fan motor pulleys are factory set for speed shown in Table 1. To change fan speeds: 1. Shut off unit power supply. 2. Loosen nuts on the 2 carriage bolts in the mounting base.
  • Page 25 NOTE: A 3 -in. bolt and threaded plate are included in the installer’s packet. They can be added to the motor support channel below the motor mounting plate to aid in raising the motor. Fig. 36 — 542J180 Indoor-Fan Motor Section NOTE: Dimensions are in inches.
  • Page 26 XIV. REPLACEMENT PARTS A complete list of replacement parts may be obtained from any Bryant distributor upon request. Fig. 39 — Cooling Charging Chart, 542J180 Units — —...
  • Page 27 Fig. 40 — Typical Wiring Diagram (542J150, 208/230-3-60 V Shown) — —...
  • Page 28 Fig. 41 — Typical Component Arrangement (542J150, 208/230-3-60 V Shown) — —...
  • Page 29 LEGEND AND NOTES FOR FIG. 40 AND 41 — Adjustable, Heat Anticipator BRK W/AT — Breaks with Amp Turns — Contactor, Compressor — Capacitor — Circuit Breaker — Cooling Compensator — Crankcase Heater — Compressor Lockout COMP — Compressor Motor —...
  • Page 30: Troubleshooting

    A functional view of the EconoMi$erIV is shown in Fig. 46. Typical settings, sensor ranges, and jumper positions are also shown. An EconoMi$erIV simulator program is avail- able from Bryant to help with EconoMi$erIV training and troubleshooting. A. EconoMi$erIV Preparation This procedure is used to prepare the EconoMi$erIV for troubleshooting.
  • Page 31 E. DCV Minimum and Maximum Position To check the DCV minimum and maximum position: 1. Make sure EconoMi$erIV preparation procedure has been performed. 2. Connect a 9-v battery to AQ (positive node) and AQ1 (negative node). The DCV LED should turn on. The actuator should drive to between 90 and 95% open.
  • Page 32 — Fixed Orifice NOTE: Circuitry shown is for single system; 542J180 units have 2 individual and independent refrigeration systems that each operate in an identical manner. Fig. 42 — Heat Pump Cooling Cycle Fig. 43 — Heat Pump Heating Cycle — —...
  • Page 33 — —...
  • Page 34 — —...
  • Page 35 INPUTS Enthalpy* Demand Control Ventilation (DCV) Outdoor Below set High (DCV LED Off) (Free Cooling LED Off) (Free Cooling LED On) Above set High (DCV LED On) (Free Cooling LED Off) (Free Cooling LED On) *For single enthalpy control, the module compares outdoor enthalpy to the ABCD set point.
  • Page 36: Index

    Air quantity limits Changeover set points Charging chart, refrigerant Clearance 5, 6 sensor Configuration Settings 15, 17 Compressor Lockout 13, 25 Lubrication Mounting Concentric duct Condensate drain Cleaning Location 3, 8 Control circuit Wiring 8, 9 Convenience outlet Crankcase heater 18, 25 Defrost thermostat Demand control ventilation...
  • Page 37 Packaged Service Training programs are an excellent way to increase your knowledge of the equipment discussed in this manual, including: • Unit Familiarization • Installation Overview A large selection of product, theory, and skills programs are available, using popular video-based formats and materials.
  • Page 38 Copyright 2006 Bryant Heating & Cooling Systems Printed in U.S.A. CATALOG NO. 5354-203...
  • Page 40: Start-Up Checklist

    REFRIGERANT DISCHARGE CIRCUIT NO. 1 VERIFY REFRIGERANT CHARGE USING CHARGING CHARTS ON PAGE 26 GENERAL ECONOMI$ERIV MINIMUM VENT AND CHANGEOVER SETTINGS TO JOB REQUIREMENTS Copyright 2006 Bryant Heating & Cooling Systems START-UP CHECKLIST (Remove and Store in Job File) SERIAL NO.: _____________________________________...

Table of Contents