Advertisement

S9 DIGITAL INPUTS

4.7
S9 Digital Inputs
4.7.1

Digital Input Functions

xxxxx SW FUNCTION:
General
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
4–48
Description
Any of the digital inputs may be selected and programmed as a separate General Switch,
Digital Counter, or Waveform Capture Input. The xxxxx term in the following menus refers
to the configurable switch input function – either the Spare Switch, Emergency Restart,
Differential Switch, Speed Switch, or Remote Reset inputs described in the following
sections.
General
GENERAL SWITCH
NAME: General
GENERAL SWITCH
TYPE: NO
BLOCK INPUT FROM
START: 0 s
GENERAL SWITCH
ALARM: Off
ASSIGN ALARM RELAYS:
Alarm
GENERAL SWITCH
ALARM DELAY: 5.0 s
RECORD ALARMS AS
EVENTS: No
GENERAL SWITCH
TRIP: Off
ASSIGN TRIP RELAYS:
Trip
GENERAL SWITCH
TRIP DELAY: 5.0 s
The above selections will be shown if the in the corresponding menu if
FUNCTION
,
EMERGENCY FUNCTION
setpoints are set to "General". Refer to the individual sections for Spare Switch, Emergency
Restart, Differential Switch, Speed Switch, or Remote Reset below for additional function-
specific setpoints.
CHAPTER 4: KEYPAD SETPOINTS
Range: 12 character alphanumeric
Only seen if function is selected as General
Range: NO (normally open), NC (normally closed)
Only seen if function is selected as General
Range: 0 to 5000 s in steps of 1
Only seen if function is selected as General
Range: Off, Latched, Unlatched
Only seen if function is selected as General
Range: None, Alarm, Aux1, Aux2, or combinations
Only seen if function is selected as General
Range: 0.1 to 5000.0 s in steps of 0.1
Only seen if function is selected as General
Range: No, Yes
Only seen if function is selected as General
Range: Off, Latched, Unlatched
Only seen if function is selected as General
Range: None, Trip, Aux1, Aux2, or combinations
Only seen if function is selected as General
Range: 0.1 to 5000.0 s in steps of 0.1
Only seen if function is selected as General
,
DIFF SW FUNCTION
, or
SPEED SW FUNCTION
369 MOTOR MANAGEMENT RELAY – QUICKSTART GUIDE