Troubleshooting By Symptoms - Samsung AC100JNCDEH/EU Service Manual

System air conditioner 4 way cassette series
Hide thumbs Also See for AC100JNCDEH/EU:
Table of Contents

Advertisement

4-3 Troubleshooting by symptoms

4-3-1 Indoor temperature sensor (open/short)
Wire remote controller display
Symptom
Failure
Is indoor temperature
sensor disconnected from the
connector in PCB?(CN412)
No
Remove the indoor temperature sensor
connector from the PCB and measure the
resistance between two terminals
In this case, is the resistance
value out of range in the temperature
table on the right?
No
Restart the system after replacing the PCB
Samsung Electronics
All manuals and user guides at all-guides.com
E121
Error of Room sensor in the indoor unit(Open/Short)
Short or leakage of the Room sensor
Yes
Restart the system after connecting
Yes
Indoor temperature sensor
to the PCB connector
<Temperature sensor
resistance value>
Current
temperature
(°C)
failure (replace)
-10
Troubleshooting
Resistance
(kΩ)
40
5.800
±3%
35
6.900
±3%
30
8.300
±3%
25
10.00
±3%
20
12.10
±3%
15
14.70
±3%
10
18.00
±3%
5
22.00
±3%
0
28.30
±3%
-5
33.90
±3%
42.30
±3%
4-13