CCN
CCN
TABLE
POINT
NAME
NAME
SPT
SAT
RAT
SFS
SF
SP
IGV
STATUS01
OAT
ECON
BP
EFRF
FLTS
EXTCLK
PED
MM
FR2
STATUS02
FR3
HS1
HS2
RH
OARH
ENTH
OAC
IAQ
STATUS03
EVAC
PRES
PURG
FSD
FRZ
HCV
STRST
UNCHT
UNCCL
STDBY
OPTST
UNOCC
IAQPG
OPTSP
OCCHT
STATUS04
OCCCL
OCCFO
NTFCL
PRESS
EVACN
SMKPG
FIRES
TIMOV
HHOVR
IAQCL
CMPA1
CPSA1
ULDA1
STATUS05
CMPA2
ULDA2
CPFA1
CMPB1
CMPB2
CPSB1
STATUS06
ULDB1
ULDB2
CPFB1
CPFB2
APPENDIX D — BACnet Points List
BACnet
OBJECT
EXPANDED NAME
NAME
SPT
Space Temperature
SAT
Supply Air Temperature
RAT
Return Air Temperature
SFS
Supply Fan Status
SF
Supply Fan Relay
SP
Duct Static Pressure
IGV
Inlet Guide Vanes
OAT
Outside Air Temperature
ECON
Economizer Damper
BP
Building Pressure
EFRF
Exhaust/Return Fan
FLTS
Filter Status
EXTCLK
External Clock Input
PED
Power Exhaust Damper
MM
Motormaster/Fan Stage 1
FR2
Condenser Fan Stage 2
FR3
Condenser Fan Stage 3
HS1
Heat Stage 1
HS2
Heat Stage 2
RH
Return/Space Humidity
OARH
Outside Air Humidity
ENTH
Enthalpy Status
OAC
Outside Air CFM
IAQ
IAQ (CO
)
2
EVAC
Evacuation
PRES
Pressurization
PURG
Smoke Purge
FSD
Fire Shutdown
FRZ
Freezestat Status
HCV
Heating Valve
STRST
Space Temperature Reset
UNCHT
Unoccupied Heating
UNCCL
Unoccupied Cooling
STDBY
Unit in Standby
OPTST
Optimal Start
UNOCC
Unoccupied
IAQPG
IAQ Purge
OPTSP
Optimal Stop
OCCHT
Occupied Heating
OCCCL
Occupied Cooling
OCCFO
Occupied Fan Only
NTFCL
Night Time Free Cooling
PRESS
Pressurization
EVACN
Evacuation
SMKPG
Smoke Purge
FIRES
Fire Shutdown
TIMOV
Timed Override
HHOVR
High Humidity Override
IAQCL
IAQ/Outdoor Air CFM Ctrl*
CMPA1
Compressor A1
CPSA1
Compressor A1 Status
ULDA1
Unloader A1
CMPA2
Compressor A2*
ULDA2
Unloader A2*
CPFA1
Compressor A1 Safety
CMPB1
Compressor B1
CMPB2
Compressor B2*
CPSB1
Compressor B1 Status
ULDB1
Unloader B1
ULDB2
Unloader B2*
CPFB1
Compressor B1 Safety
CPFB2
Compressor B2 Safety*
BACnet
BACnet
OBJECT
OBJECT
TYPE
PROPERTIES
AI
RO
AI
RO
AI
RO
BI
RO
BO
RO
AI
RO
AI
RO
AI
RO
AO
RO
AI
RO
BO
RO
BI
RO
BV
RW
AO
RO
BO
RO
BO
RO
BO
RO
BO
RO
BO
RO
AI
RO
AI
RO
BI
RO
AI
RO
AI
RO
BV
RW
BV
RW
BV
RW
BV
RW
BI
RO
AO
RO
AI
RO
BV
RO
BV
RO
BV
RO
BV
RO
BV
RO
BV
RO
BV
RO
BV
RO
BV
RO
BV
RO
BV
RO
BV
RO
BV
RO
BV
RO
BV
RO
BV
RO
BV
RO
BV
RO
BO
RO
BI
RO
BO
RO
BO
RO
BO
RO
BI
RO
BO
RO
BO
RO
BI
RO
BO
RO
BO
RO
BI
RO
BI
RO
109
BACLink
DISPLAY FORMAT/
DEFAULT
ENGINEERING UNITS
TEMPLATE
Y
–10 to +245 F
Y
–10 to +245 F
Y
–10 to +245 F
Y
on/off
Y
on/off
Y
0.0 to 5.0 in. wg
Y
0 to 100%
–40 to +245 F
Y
0 to 100%
–0.5 to +0.5 in. wg
on/off
dirty/clean
Y
on/off
0 to 100%
on/off
on/off
on/off
Y
on/off
Y
on/off
0 to 100%
0 to 100%
hi/low
0 to 50,000 CFM
0 to 5000 PPM
alarm/norm
alarm/norm
alarm/norm
alarm/norm
alarm/norm
0 to 100%
no/yes
no/yes
no/yes
no/yes
no/yes
no/yes
no/yes
no/yes
no/yes
no/yes
no/yes
no/yes
no/yes
no/yes
no/yes
no/yes
no/yes
no/yes
no/yes
Y
on/off
on/off
on/off
on/off
on/off
alarm/norm
Y
on/off
on/off
on/off
on/off
on/off
alarm/norm
alarm/norm

Advertisement

Table of Contents
loading

This manual is also suitable for:

JpNp034-07450fbFpJbNb ... Show all

Table of Contents