15 Specifications
Housing
Dimensions
Protection
Connections
Power Supply
(depending on the model)
Power Absorption
Display
Inputs
Relay Outputs
UL Ratings
Data Storing
Internal Clock Back-up
Kind of Action
Pollution Grade
Software Class
Rated Impulsive Voltage
Overvoltage Category
Temperature
Relative Humidity
Measuring and Regulation Range
Resolution
Accuracy (ambient temp. 25°C)
Table 15-1 - XR35CX Specifications
20 • XR35CX I&O Manual
Self extinguishing ABS
Case: Front: 32 mm x 74 mm, Depth: 60 mm
Panel Mount: 71 mm x 29 mm panel cut-out
IP 20
Frontal: IP65
Screw terminal block ≤ 2.5 mm
24VAC, ±10%
230VAC, ±10%, 50/60Hz 110VAC, ±10%, 50/60Hz
34VA max
3 digits, red LED, 14.2 mm high
Up to 4 NTC, CtC, or PT1000 probes
Digital: Free voltage contact
Compressor:
120 V, 50/60 Hz, 1/4 HP, 30k cycles
240 V, 50/60 Hz, 1/2 HP, 30k cycles
AUX/Light/Defrost N. O.:
120/240 V, 50/60 Hz, 10A, Resistive, 30k cycles
120/240 V, 50/60 Hz, B300, Pilot Duty, 6k cycles
AUX/Light/Defrost N. C.:
120/240 V, 50/60 Hz, 10A, Resistive, 30k cycles
120/240 V, 50/60 Hz, B300, Pilot Duty, 6k cycles
On the non-volatile memory (EEPROM)
24 hours
1B
2
A
2500V
II
Operating: 0 to 55°C
Storage: -30 to 85°C
20 to 85% (no condensing)
NTC probe: -40 to 110°C (-40 to 230°F)
PT1000 probe:
-100 to 150°C
(-148 to 302°F)
0.1°C or 1°C or 1 °F (selectable)
±0.7°C ±1 digit
2
wiring
026-1203 Rev 3 03-FEB-2015
Terminals 3 and 1
Terminals 7 and 1
Terminals 8 and 1