Daikin RXYSQ4T8VB Series Installer And User Reference Manual page 58

Vrv iv-s system air conditioner
Table of Contents

Advertisement

17
|
Unit installation
Installer and user reference guide
58
Height of windbreaker≥1.5×height of outdoor unit
Mind the service space requirements when installing the windbreaker.
a
d
c
a Sea wind
b Building
c Outdoor unit
d Windbreaker
Strong winds (≥18 km/h) blowing against the outdoor unit's air outlet causes short
circuit (suction of discharge air). This may result in:
deterioration of the operational capacity;
frequent frost acceleration in heating operation;
disruption of operation due to decrease of low pressure or increase of high
pressure;
a broken fan (if a strong wind blows continuously on the fan, it may start rotating
very fast, until it breaks).
It is recommended to install a baffle plate when the air outlet is exposed to wind.
Turn the air outlet side towards the building's wall, fence or screen.
a Make sure there is enough installation space
Set the air outlet side at a right angle to the direction of the wind.
a
a Prevailing wind direction
b Air outlet
d
c
b
a
RXYSQ4~6T8V/YB
VRV IV-S system air conditioner
4P482277-1B – 2020.10

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents