Siemens 7XT71 Series Manual page 17

Controller unit
Table of Contents

Advertisement

Available languages

Available languages

7XT7100-0*A00/DD
- Fast transients
IEC 60 255-22-4
and IEC 61 000-4-4, class III
- Conducted disturbances induced by
radio-frequency fields, amplitude modulated
IEC 61 000-4-6, class III
- Power frequency magnetic field
IEC 61 000-4-8, class IV
IEC 60 255-6
Further EMC tests; immunity (type tests)
- Oscillatory surge withstand capability
ANSI/IEEE C37.90.1
- Fast transient surge withstand capability
ANSI/IEEE C37.90.1
- Radiated electromagnetic interference
ANSI/IEEE C37.90.2
- Damped oscillations
IEC 60694
IEC 61000-4-12
EMC tests; emission (type tests)
Standard:
- Conducted interference voltage, aux. voltage
CISPR 22, EN 55022, class B
- Interference field strength
CISPR 22, EN 55022, class B
C53000-B119U-C128-1
2 kV; 5/50 ns; 5 kHz;
burst length 15 ms;
repetition rate 300 ms; both polarities;
R
= 50 ohms; duration 1 min
i
10 V; 150 kHz to 80 MHz; 80 % AM;
1 kHz
30 A/m continuous; 300 A/m for 3 s;
50 Hz; 0.5 mT; 50 Hz
2.5 kV to 3 kV (peak);
1 MHz to 1.5 MHz,
decaying oscillation; 50 surges per s;
duration 2 s; R
= 150 to 200 ohms
i
4 kV to 5 kV; 10/150 ns;
50 surges per s; both polarities;
duration 2 s; R
= 80 ohms
i
35 V/m
25 MHz to 1000 MHz;
2.5 kV (peak, alternating polarity);
1 MHz, 10 MHz and 50 MHz,
decaying oscillation; R
EN 50081-1 (generic standard)
150 kHz to 30 MHz
30 MHz to 1000 MHz
English
= 200 ohms
i
17

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

7xt7100-0 a00/dd series7xt7100-0ba007xt7100-0ea00

Table of Contents