Installation; Lighting Instructions; Shutdown Instructions; Servicing Instructions - Stanley ST-10KW-GFA-E Manual

Mobile gas fired forced air heater
Table of Contents

Advertisement

Available languages

Available languages

The Propane (LPG) gas pressure
WARNING
regulator and hose assembly supplied
with the heater must be used without alteration.

iNstallatioN

minimum ventilation requirements: room volume should not
be less than 100 m³; minimum ventilation of 25 cm² per kw of
heat input subject to a minimum of 250 cm².
1. Inspect LPG supply cylinder to ensure it is in good condition.
2. Connect power cord to electrical supply outlet.
3. Connect Gas supply hose to heater. Required hose and
regulator is to be 1.5 metres max and 1.0 meter min. in
length, and type EN12864). Connect other end (regulator) to
an LPG supply cylinder.
Be careful to avoid torsional stresses in
WARNING
the flexible tubing (regulator hose).
Use the appropriate LPG supply cylinder
CAUTION
listed below.
ST-10KW-GFA-E : 9 Kg to 45 Kg LPG cylinder
ST-15KW-GFA-E : 9 Kg to 45 Kg LPG cylinder
ST-30KW-GFA-E : 9 Kg to 45 Kg LPG cylinder
ST-40KW-GFA-E : 9 Kg to 45 Kg LPG cylinder
Note: Optimum efficiency is achieved when the heater uses
the appropriate full LPG supply cylinder.
4. Slowly open the LPG supply cylinder. Leak test all gas
connections with 50/50 soap and water solution prior to start-up
to ensure the heater is connected properly. Soap bubbles
indicate a gas leak. DO NOT use a match or flame to test for
gas leaks.
Note: Consult local regulations when planning to install an
air temperature control.
chaNgiNg lpg supplY cYliNders
1. When changing LPG supply cylinders, be sure this is done in a
flame-free atmosphere.

lightiNg iNstructioNs

1. Inspect heater before each use. Switch the electrical power
switch to ON and check if fan is operating correctly.
2. Wait five (5) minutes for any gas to clear. Smell for gas. If none
is evident, proceed to the next step.
3. Push in the flameout protector with your right hand, then press
the igniter with your left hand to light the burner.
4. Keep the flameout protector pushed in for an additional 30
seconds after lighting.
5. If burner does not stay lit, wait one minute and repeat steps
3 and 4. Try holding in the flameout protector for longer after
lighting.
6. Once burner is lit, adjust the Control Valve to desired heat level.
© 2015, Pinnacle Products International, Inc.

shutdowN iNstructioNs

1. After use, turn the control knob at the LPG supply cylinder
clockwise to the CLOSED position.
2. Turn the Control Valve on the heater all the way clockwise until
it stops so the valve is closed.
3. Disconnect heater from power supply, and disconnect regulator
from the LPG supply cylinder.

serviciNg iNstructioNs

These instructions are intended to be used only by competent
persons and they shall provide detailed instructions for carrying
out all servicing operations authorized by the manufacturer.
All special tools, materials or servicing aids necessary for the
correct servicing of the appliance shall be specified. Be sure to
check heater for soundness.
-
Heater surface temperature must be cold before initiating
service, cleaning or storage.
-
Maintenance and repair must be carried out by trained
personnel only, at least 2 times per season.
-
Before commencing service maintenance disconnect the unit
from the electrical power and the gas supply.
-
Check the LPG supply hose condition and change if necessary.
-
Check the ignition unit, safety thermostat, and thermocouple
condition and ensure that they are clean. If flame pattern
appears irregular, check nozzle. Wear eye protection when
performing these checks.
-
Clean inside the heater unit and the fan blade with compressed
air. Heater is operating correctly when fan is running, flame is
present and soap test showed no leaks.

loNg term storage

Always disconnect the heater from the LPG supply cylinder
Disconnect heater from LPG supply
WARNING
cylinder when not in use.
before putting the heater into storage. If for any reason the heater
is to be stored indoors, the heater MUST be disconnected from
the LPG supply cylinder, and the cylinder stored outdoors in a
well-ventilated area, and out of the reach of children.
The plastic valve plug or valve cover supplied with the LPG
supply cylinder must be re-installed on the valve to protect the
fitting from damage.
this appliance is not intended for use by
persons (including children) with reduced
physical, sensory or mental capabilities,
or lack of experience and knowledge,
unless they have been given supervision or
instruction concerning use of the appliance
by a person responsible for their safety.
children should be supervised to ensure that
they do not play with the appliance.
if the power cord is damaged, it must be
replaced by the manufacturer, its service
agent or similarly qualified persons in order
to avoid a hazard.
- Note: in some countries, there may be differences
in the requirements listed in this manual. in these
cases, contact your local dealer for possible
variations from requirements in this manual.
9

Advertisement

Table of Contents
loading

This manual is also suitable for:

St-15kw-gfa-eSt-30kw-gfa-eSt-40kw-gfa-e

Table of Contents