Modbus Register List:

DINCon II Register List:
ADDRESS
ACCESS
90-99
R
100
R
101-102
R
103
R/W
104-105
R/W
106
R/W
107
R/W
108
R/W
109
R/W
110
R/W
111
FORMAT
VALUE
ASCII String
DINCon Serial Number
16 bit
Model Number
0 = DINCon
IEEE Float
Software Version
16 bit
Reset Control
bit 0 = System Reset
bit 1 = Reset to Defaults
bit 2 = Alarm Reset
16 bit
Modbus Address
104 may need be set to 0xa55a (hex)
registers 104-109 must be written as a block
105 contains Modbus address
16 bit
Modbus Mode
0 = RS485 RTU
1 = RS485 ASCII
2 = RS232 RTU
3 = RS232 ASCII
4 = USB RTU
5 = USB ASCII
6 = TCP
16 bit
Modbus Baud Rate (38400 default)
0 = 1200
1 = 2400
2 = 4800
3 = 9600
4 = 19200
5 = 28800
6 = 38400
7 = 57600
8 = 115200
16 bit
Modbus Serial Word Length ( 7 or 8)
16 bit
Modbus Serial Parity (Even, 1 Stop Bit default)
0 = none, 2 Stop Bits
1 = odd, 1 Stop Bit
2 = even, 1 Stop Bit
16 bit
TCP Address P1
TCP Address P2
15
Default
0
0xa55a
10
0
6
8
2
192
168