End Position When Reference Variable Is Below Limit Value Setp_Cutoff_Dec; End Position When Reference Variable Is Above Limit Value Setp_Cutoff_Inc - Samson 3785 Mounting And Operating Instructions

Profibus positioner
Table of Contents

Advertisement

List of parameters
Diagnosis extension
DIAGNOSIS_EXTENSION
Message type:
States:
End position when
reference variable is above
the limit value
SETP_CUTOFF_INC
Default:
End position when
reference variable is
below the limit value
SETP_CUTOFF_DEC
Default:
Fail-safe action
FSAFE_TYPE
States:
Default:
Fail-safe position
ACTUATOR_ACTION
States:
Fail-safe time
FSAFE_TIME
Range:
Default:
52
EB 8382-1 EN
Additional manufacturer-specific detailed device information, coded bit-wise
encoded which enables several simultaneous messages, see also Chapter 9.
A: Dynamic messages; they are automatically reset by readout.
R: Static messages; they are retained, as long as the event is imminent in the field device.
0: No message
1: Message active
If the reference variable exceeds the entered limit, the valve moves in the end position,
corresponding to 100 % of the reference variable. Hysteresis 1%.
When the value is 125 %, the function is deactivated.
99 %
Caution: Since the actuator will automatically be filled with air or vented when this
function is executed, the control valve moves in its absolute end positions.
Constraints specified in the function "travel range" or "travel limit" do not apply here.
This function must be deactivated if unacceptably high positioning forces result from
the complete filling/venting action.
If the reference variable falls below the entered limit, the valve moves in the end
position, corresponding to 0 % of the reference variable. Hysteresis 1%.
When the value is −2.5 %, the function is deactivated.
1 %
Caution: Since the actuator will automatically be filled with air or vented when this
function is executed, the control valve moves in its absolute end positions.
Constraints specified in the function "travel range" or "travel limit" do not apply here.
This function must be deactivated if unacceptably high positioning forces result from
the complete filling/venting action.
Defines reaction when communication failure or device start-up is recognized.
0 = Adjust to fail-safe value
1 = Adjust to/save last valid set point
2 = Move to fail-safe position determined by spring action
1
Fail-safe position of the actuator in the event of air/power failure or start-up.
Read-only value, automatically determined during the initialization process
0 = Not initialized
1 = Opening in direction of the 100 % position
2 = Closing in direction of the 0 % position
3 = None/saving (position is retained)
If the DP watchdog detects a communication failure, the fail-safe action is triggered
after the fail-safe time has elapsed.
0 to 3600s
10 s

Advertisement

Table of Contents
loading

Table of Contents