Delay Settings: S1 and S2
Use the delay function to slow the response, and compensate for turbulence or false
readings.
• Delay potentiometer P1 can be adjusted to set a delay time from 1 to 60 seconds.
• Two separate delay settings are controlled by S1 and S2:
– for alarm activation (alarm ON)
– for alarm de-activation (alarm OFF)
• When switches are OFF (open) the delay is enabled.
• The position of Failsafe switch S3 determines how S1 and S2 function.
S3- ON
S3- OFF
Set-up mode / run mode: S5
S5-ON
S5-OFF
Test settings: S4
When S4 is set to ON, it inverts the signal, allowing you to test the delay settings from P1, or
to verify that S1 and S2 are in the correct position.
S4-ON
S4-OFF
7.1.1.4

Setup

It is essential to check settings during the process itself, and confirm that they are correct,
before regular operation commences.
Initial setup can be carried out prior to mounting into the process, but it is extremely
important to calibrate the unit and adjust the sensitivity on the product itself.
7.1.1.5

Start up

After Pointek CLS200 is properly mounted apply power to the unit. The green LED (L3) glows,
indicating the unit is powered and operational.
Pointek CLS200/CLS300 standard
Operating Instructions, 05/2021, A5E47827796-AA
High alarm/ over-
fill protection
Low alarm/dry
run protection
Set-up mode
Run mode
Enable test
Normal operation
WARNING
S1-ON
disables delay of alarm de-activation (alarm OFF)
S2-ON
disables delay of alarm activation (alarm ON)
S1-ON
disables delay of alarm activation (alarm ON)
S2-ON
disables delay of alarm de-activation (alarm OFF)
Use this setting only during trip-point set-up.
Use this setting during normal operation after set-up is complete.
Observe the response of the output status and sensor status LEDs
to verify the delay interval set by potentiometer P1.