Cross sections are typically 4×95 mm

Terminal [X350] data for the control cables

Terminal type: Spring-cage connection
Conductor stripping length: 8...10 mm
Conductor max. size: 4 mm
Conductor min. size: 0.08 mm
with ferrule)

DC connection data

See
Selecting the energy storage (page

Auxiliary circuit current consumption

Auxiliary circuit current consumption varies depending on the actual drive configuration and
options. Contact ABB for the delivery-specific value.

Energy efficiency data (ecodesign)

Energy efficiency data is not provided for the drive/unit. The multidrives are not in the scope
of the EU ecodesign requirements (Regulation EU/2019/1781) or the UK ecodesign
requirements (Regulation SI 2021 No. 745).

Protection classes

Degrees of protection
(IEC/EN 60529)
Enclosure types (UL50)
Overvoltage category
(IEC/EN 60664-1)
Protective class
(IEC/EN 61800-5-1)

Ambient conditions

Environmental limits for the drive are given below. The drive is to be used in a heated,
indoor, controlled environment.
Installation site altitude
2
, 4×120 mm
2
(solid), 2.5 mm
2
(solid), 0.08 mm
24).
IP42 (standard), IP54 (option +B055)
UL Type 1 (standard), UL Type 12 (option +B055). For indoor use only.
III, except for auxiliary power connections (fan, control, heating, lighting, cooling
unit pump etc) which are category II.
I
Operation
installed for stationary
use
0...2000 m (0...6562 ft)
above sea level. For alti-
tudes over 2000 m, contact
ABB.
Output derated above 1000
m (3281 ft).
2
or 4×150 mm
2
(stranded)
2
(stranded, no ferrule), 0.14 mm
Storage
in the protective package
-
Technical data 57
2
.
2
(stranded,
Transportation
in the protective package
-