Eaton Ulusoy URING36 - LLF User Manual

Eaton Ulusoy URING36 - LLF User Manual

Compact switchgear with fuse
Hide thumbs Also See for Ulusoy URING36 - LLF:

Advertisement

Quick Links

www.eaton.com
Ulusoy URING36 - LLF - 3 Way
Compact Switchgear with Fuse
User Manual

Advertisement

Table of Contents
loading

Summary of Contents for Eaton Ulusoy URING36 - LLF

  • Page 1 Ulusoy URING36 - LLF - 3 Way Compact Switchgear with Fuse User Manual...
  • Page 2: Table Of Contents

    TABLE OF CONTENTS 1. CAUTION..........................1 2. HANDLING AND TRANSPORT....................2 3. STORAGE..........................3 4. MAIN FEATURES........................4 5. SWITCHGEAR MAIN EQUIPMENTS..................4 6. DIMENSIONS..........................5 7. ACCESSORIES........................5 URING36-L SF6 INSULATED RMU SWITCHGEAR WITH LBS SWITCHGEAR INTRODUCTION....................6 DIMENSIONS (in millimeters)..................7 Checks Before Energisation the URING36-L Switchgear..........7 CHECK TO BE PERFORMED BEFORE POWERING URING36-L SWITCHGEAR......8 LV Board Control Panel of URING36-L................8 Energizing the Incoming MV Cables................9...
  • Page 3: Caution

    Ulusoy URING36 - LLF - 3 Way Compact Switchgear with Fuse User Manual May 2020 www.eaton.com...
  • Page 4: Handling And Transport

    Lifting of a URING switchgear with chains Ulusoy URING36 - LLF - 3 Way Compact Switchgear with Fuse User Manual May 2020 www.eaton.com...
  • Page 5: Storage

    Otherwise, the manometer needle may indicate an incorrect value, even if the equipment’s internal gas pressure is correct. Ulusoy URING36 - LLF - 3 Way Compact Switchgear with Fuse User Manual May 2020 www.eaton.com...
  • Page 6: Main Features

    Switch & Earth Switch Position Indicator Operation Sequence Motor & Manuel Selection Switch 12 - 18 - Earth Switch Operation Hole Manometer LV Panel Cover Button Ulusoy URING36 - LLF - 3 Way Compact Switchgear with Fuse User Manual May 2020 www.eaton.com...
  • Page 7: Dimensions

    6. DIMENSIONS 1332 1062 Single Line Scheme 7. ACCESSORIES Protection Relay Toroidal Current Bushing Transformer Vacuum CB MV Fuse LV Compartment Ulusoy URING36 - LLF - 3 Way Compact Switchgear with Fuse User Manual May 2020 www.eaton.com...
  • Page 8: Uring36-L Sf6 Insulated Rmu Switchgear With Lbs

    Mechanical Assembly Motor (Optional.) Single Line Scheme LV Control Board (Lv Panel) Mechanism Section Cable Connection Terminal Cable Connection Clamps Main Busbar Connection Terminals Ulusoy URING36 - LLF - 3 Way Compact Switchgear with Fuse User Manual May 2020 www.eaton.com...
  • Page 9: Dimensions (In Millimeters)

    Check if there are foreign objects in the switchgear. Check the connections of the switchgear. Place the switchgear front cover. Check if the front cover is placed correctly. Ulusoy URING36 - LLF - 3 Way Compact Switchgear with Fuse User Manual May 2020 www.eaton.com...
  • Page 10: Check To Be Performed Before Powering Uring36-L Switchgear

    Motor Assembly Paco Switch (Remote/Local) Remote Trip Control Socket Voltage indicator After manually assembling load break switch mechanism, operate it with buttons a few times. Ulusoy URING36 - LLF - 3 Way Compact Switchgear with Fuse User Manual May 2020 www.eaton.com...
  • Page 11: Energizing The Incoming Mv Cables

    Turn the earthing disconnector OFF from both sides. • • Perform the required test for check the cable healthy. • Perform the required test. Ulusoy URING36 - LLF - 3 Way Compact Switchgear with Fuse User Manual May 2020 www.eaton.com...
  • Page 12: Operational Instructions

    Switchgear front cover is open. After closing the switchgear front cover; Earthing disconnector is ON, LBS is OFF , Switchgear front cover is closed. Ulusoy URING36 - LLF - 3 Way Compact Switchgear with Fuse User Manual May 2020 www.eaton.com...
  • Page 13: Earthing Switch Operation

    LV fuses (MCB) ON. After the charge of the closing spring: Earthing switch is OFF , Closing spring is charged LBS is ON. Ulusoy URING36 - LLF - 3 Way Compact Switchgear with Fuse User Manual May 2020 www.eaton.com...
  • Page 14 To turn the LBS OFF . Press the OFF(0) button. Position of LBS after turning OFF: Earthing switch is OFF , LBS is OFF . Ulusoy URING36 - LLF - 3 Way Compact Switchgear with Fuse User Manual May 2020 www.eaton.com...
  • Page 15: Safe Operation

    SAFE OPERATION Switchgear front cover can only be removed or attached when the earthing disconnector is ON. Ulusoy URING36 - LLF - 3 Way Compact Switchgear with Fuse User Manual May 2020 www.eaton.com...
  • Page 16: Replacing The Voltage Indicator

    Check the polarity of the connection made for DC supply source. ELECTRIC TERMINAL SCHEME URING36-L Load Disconnector Earting Disconnector DC Auxiliary Supply Auxiliary Contacts Auxiliary Contacts OFF - ON Ulusoy URING36 - LLF - 3 Way Compact Switchgear with Fuse User Manual May 2020 www.eaton.com...
  • Page 17: Uring36-F Sf6 Insulated Rmu Switchgear With Lbs & Fuse

    Operation Sequence Label Remote Control Socket Single Line Scheme LV Board Mechanism Section MV Fuse Housings Cable Connection Terminal Cable Connection Clamps Main Bus-bar Connection Terminals Ulusoy URING36 - LLF - 3 Way Compact Switchgear with Fuse User Manual May 2020 www.eaton.com...
  • Page 18: Fuse Selection For Transformer Protection

    CURRENT In (A) NOTE: If the switchgear operation voltage is different than 36kV, consult the sales department for appropriate fuse nominal value and fuse adapter. Ulusoy URING36 - LLF - 3 Way Compact Switchgear with Fuse User Manual May 2020 www.eaton.com...
  • Page 19: Placing The Fuses In The Switchgear

    Ulusoy URING36 - LLF - 3 Way Compact Switchgear with Fuse User Manual May 2020 www.eaton.com...
  • Page 20: Dimensions (In Millimeters)

    Check if the front cover is placed correctly. If the front cover is not fixed, operation hole cannot be placed in spring charging hole. Ulusoy URING36 - LLF - 3 Way Compact Switchgear with Fuse User Manual May 2020 www.eaton.com...
  • Page 21: Use Test To Be Performed Before Energizing Uring36-F Switchgear

    Button Operate the LBS and earth switch a few times. URING36-F Switchgear LV Board Voltage Remote Control Indicator Socket Notification Relay+ Signal Light Box Ulusoy URING36 - LLF - 3 Way Compact Switchgear with Fuse User Manual May 2020 www.eaton.com...
  • Page 22: Operational Instructions

    Switchgear front cover is open. After closing the switchgear front cover; Earthing Switch is ON, LBS is OFF , Switchgear front cover is closed. Ulusoy URING36 - LLF - 3 Way Compact Switchgear with Fuse User Manual May 2020 www.eaton.com...
  • Page 23: Earthing Disconnector Maneuvers

    LV fuses are ON. After the charge of the closing spring: Earthing switch is OFF , Closing spring is charged LBS is OFF . Ulusoy URING36 - LLF - 3 Way Compact Switchgear with Fuse User Manual May 2020 www.eaton.com...
  • Page 24 To turn the LBS OFF , press the OFF button. Position of LBS after turning OFF: Earthing switch OFF , LBS is OFF . Ulusoy URING36 - LLF - 3 Way Compact Switchgear with Fuse User Manual May 2020 www.eaton.com...
  • Page 25: Safe Operation

    (cables). SAFE OPERATION Switchgear front cover can only be removed when the earthin switch ON. Ulusoy URING36 - LLF - 3 Way Compact Switchgear with Fuse User Manual May 2020 www.eaton.com...
  • Page 26: Replacing The Voltage Indicator

    Check if the MV fuses are steady. Closing spring cannot be charged If one of the fuses is blown, replace the fuses. ELECTRIC TERMINAL SCHEME Ulusoy URING36 - LLF - 3 Way Compact Switchgear with Fuse User Manual May 2020 www.eaton.com...
  • Page 27 Eaton’s mission is to improve the quality of life and the environment through the use of power management technologies and services. We provide sustainable solutions that help our customers effectively manage electrical, hydraulic, and mechanical power - more safely, more efficiently, and more reliably.