Nailor 1290F Quick Start Manual

Dynamic round fire damper
Hide thumbs Also See for 1290F:

Advertisement

Quick Links

QUALIFICATIONS:
• UL 555 & CAN/ULC-S112 CLASSIFIED DYNAMIC FIRE
DAMPER 1 1/2 hr. Label (File # R9492).
• Meets NFPA 80, 90A and 101 as well as IBC and NBC
(Canada) Building Code requirements.
• California State Fire Marshal: Fire Damper Listing No.
3225-0935:0101.
• Maximum velocity: 2000 fpm @ 4" w.g. (10 m/s @ 1 kPa).
Model 1290F fire damper is ideal for applications where building
codes require a fire damper for the protection of ductwork
penetrations in walls or floors that have a fire resistance rating of
up to 2 hours. The 1290F is classified for use in dynamic "fans
on" systems where the HVAC system remains operative in the
event of a fire. Damper closure under airflow is assured.
The 1290F is an economical true round fire damper designed
and qualified specifically for point-of-origin fire containment
where round ductwork passes through metal or wood stud
drywall partitions and masonry walls or floors.
Features include the industry proven over-center knee lock
design with high torque spring/fusible link closure. The 1290F is
supplied as standard with a crank arm and locking screw which
holds the damper in the fully open position, but may also be used
for system balancing if required.
STANDARD CONSTRUCTION:
Frame:
20 ga. (1.0) galvanized steel integral sleeve and
retaining plates.
Blade:
2 x 20 ga. (1.0) galv. steel laminated together.
14 ga. (2.0) equivalent thickness.
Linkage:
Jackshaft to blade.
Bearings:
1/ 2" (13) dia. self-lubricating oilite bronze.
Axles:
1/ 2" (13) dia. plated steel double bolted to blades.
Jackshaft:
1/2" (13) dia. cadmium plated steel. Supplied with
factory mounted hand locking quadrant.
Fusible Link: 165°F (74°C) standard. 212°F (100°C) available.
Sizes (Duct Dia.):
Minimum
Maximum
6" (152) dia.
24" (610) dia.
Note: Dampers available in 1" (25) increments. Vertical or horizontal
installation.
OPTIONS:
BS
Stainless steel bearings
MLS-300 Position indicator switch pack
(8" (203) dia. minimum size required).
SCHEDULE TYPE:
PROJECT:
ENGINEER:
CONTRACTOR:
Nailor Industries Inc. reserves the right to change any information concerning product or pricing without notice.
DYNAMIC ROUND FIRE DAMPER
1 1/2 HR. LABEL • VERT. OR HORIZ.
FOR USE IN DYNAMIC OR STATIC SYSTEMS
MODEL: 1290F
NOM. DIA.
- 1/8" (3)
(Retaining Plates not shown)
INSTALLATION
RETAINING PLATES
INCLUDED
ACTUATOR
DRIVE
SHAFT
5 3/4" (146)
16" (406) STANDARD
Wall Thickness
Min. Sleeve Length
4 to 8 (102 to 203)
16 (406)
10 to 12 (254 to 305)
20 (508)
14 to 16 (356 to 406)
24 (610)
For installation instructions, see IOM-1290FINST.
Dimensions are in inches (mm).
DATE
B SERIES
SUPERSEDES DRAWING NO.
4 - 28 - 14
1200
11 - 28 - 11
CCW
TO
OPEN
1290F-1

Advertisement

Table of Contents
loading

Summary of Contents for Nailor 1290F

  • Page 1 Dimensions are in inches (mm). PROJECT: DATE B SERIES SUPERSEDES DRAWING NO. ENGINEER: CONTRACTOR: 4 - 28 - 14 1200 11 - 28 - 11 1290F-1 Nailor Industries Inc. reserves the right to change any information concerning product or pricing without notice.
  • Page 2: Standard Construction

    Dimensions are in inches (mm). PROJECT: DATE B SERIES SUPERSEDES DRAWING NO. ENGINEER: CONTRACTOR: 4 - 28 - 14 1200 11 - 28 - 11 1290F-SS-1 Nailor Industries Inc. reserves the right to change any information concerning product or pricing without notice.
  • Page 3 Dimensions are in inches (mm). PROJECT: DATE B SERIES SUPERSEDES DRAWING NO. ENGINEER: CONTRACTOR: 7 - 20 - 07 FD - ACC 12 - 4 - 02 MLS-300-2 Nailor Industries Inc. reserves the right to change any information concerning product or pricing without notice.
  • Page 4: Performance Data

    TRUE ROUND FIRE D MPERS PERFORMANCE DATA: MODEL SERIES: 1290F - 1 1/2 HOUR LABEL AND 1290F-SS - 1 1/2 HOUR LABEL PRESSURE DROP 1290F Maximum Performance Ratings (174) UL 555 Fire Rating 1 1/2 Hour (150) Maximum Velocity 2000 fpm (10 m/s)
  • Page 5 4. Splice clips, 20 gauge (1.0) galvanized steel (1290F) or stainless steel (1290F-SS), two pairs for each plate. 5. Steel or wood runner. 6. Retaining clip - 1" x 1" x 1" (25 x 25 x 25) 20 gauge (1.0) galvanized steel (1290F) or stainless steel (1290F-SS) angle (see note 5). 7. #10 sheet metal screw 8.
  • Page 6: General Installation

    If damper frame/sleeve and connecting duct are 16 gauge (1.61), a rigid duct connection may be used. 8. Maximum Damper Size: 24" (610) dia. Minumum size is 6" (152) dia. REFER TO THE APPROPRIATE NAILOR INSTALLATION INSTRUCTION SUPPLEMENTS FOR ADDITIONAL INFORMATION OR SPECIAL...
  • Page 7 (making sure temperature rating is visible) and locate in the pin grooves (C). See Detail 2. Page 1 of 2 3 /16 IOM-MBFDIMP Page 2.094 Nailor Industries Inc. reserves the right to change any information concerning product or specification without notice or obligation.
  • Page 8: Spare Parts List

    5. Manually open the damper to 100% full open position (D). See Detail 3. 6. Tighten the bolt on the crank arm (E). See Detail 3. Reopening spring assisted fire dampers may be extremely difficult and in some cases, impossible. If it is determined that the damper is impossible or impractical to test or reopen, a thorough examination of the blade path is required to ensure that nothing will prevent the damper...
  • Page 9 AT SPLICE POINTS INDICATED INSIDE SWITCH BOX) Figure 1. MLS-300 Wiring Schematic. Page 1 of 2 Dimensions are in inches (mm). 8/07 IOM-MLS3N Page 2.102 Nailor Industries Inc. reserves the right to change any information concerning product or specification without notice or obligation.
  • Page 10 Electrical Connections: 1. Remove cover of junction box. There are four or six coded color 120 VAC. (24 VAC) wires. Four wires are the MLS-300 position indicator package. If ADDITIONAL ACTUATOR(S) six wires are present, the additional two are the field connection IF REQUIRED for either an electric actuator or an EP switch for a pneumatic actuator.

Table of Contents