Installation - Intermatic IDIGITAL DT104 Instructions And Warranty

24-hour digital time switch
Table of Contents

Advertisement

Available languages

Available languages

INSTALLATION

Preparing the Time Switch
1. Remove the mechanism from the case by depressing
the catch at the top of the case and pulling out, as
shown in FIG. 1.
2. Set the voltage selector for the desired input voltage.
The Time Switch is shipped with voltage set for 277
VAC. To operate at 120, 208 or 240 VAC, move the
selector switch to the desired setting as marked
on the circuit board. See FIG. 2.
3. The timer is shipped with DST (Daylight Saving Time)
enabled. To disable DST, move the jumper from Spare
to DST. See FIG. 2.
4. Decide whether you want to control multiple loads
simultaneously (SIM), independently (IND), or with a
2-second pulse (PUL) (e.g., for use with mechanically
held contactors or bell ringing applications), and make
sure the jumper is positioned accordingly. See location
B in Rear View above and detail at the right. See FIG. 2.
(The unit is shipped with the loads set for IND.)
5. Choose and remove the selected knockout(s) from the
enclosure.
Note: There are five 1/2" to 3/4" combination knockouts
available. There are two on the bottom of the
enclosure, one on each side, and one on the rear.
If a 3/4" knockout is needed, remove the 1/2"
knockout first, then the 3/4" knockout.
Mounting the Time Switch
1. Mount the enclosure in the desired location using the
three mounting holes provided. Position at eye level if
possible, providing space to the left of the enclosure for
the cover to swing open. See FIG. 3.
2. Replace the mechanism in the enclosure.
Connecting the Wires
1. Lift the left side of the plastic insulator off the retaining
post and pivot it up and away to expose the terminal
strip. See FIG. 4.
2. Strip the supply and load wires to 1/2". Use #14-#12
AWG wires, rated at least 75°C (167°F)-COPPER
conductors ONLY.
3. Insert wire ends under proper terminals and tighten
screws to 10.5 lbf-in. See FIG. 5a through FIG. 5d
4. Connect the ground wire to the grounding terminal at
the bottom of the enclosure. See FIG. 4.
5. Replace the plastic insulator on the retaining post.
Note: If the Time Switch is being powered from a different
circuit than the load, you do not need to install the
jumper wire. If the Time Switch is being powered from
the same circuit as the load, install the jumper wire.
IDIGITAL — 24-Hour Digital Time Switch
FIG. 1
Back of Timer
Mechanism
FIG. 2
Setting the Voltage, DST, and SIM/IND/PUL
FIG. 3
MODE
ENTER
ON /
ON /
RESET
NEXT
+
OFF
OFF
Clear Mem
Clear Entry
BATTERY
Wire
Terminal
Ground
Terminal
FIG. 4
Plastic Insulator and Wire Terminals
Timer Power
1
L2/N
Line 1
120/208/240/277 VAC Input
Install jumper only if timer input
and load voltage are the same
FIG. 5a
DT104 configured for pulse SPST load with jumper set to PUL
Timer Power
1
L2/N
2
Line 1
120/208/240/277 VAC Input
Removing the Mechanism
Mounting Hole
Enclosure Mounting Holes
MODE
ENTER
ON /
ON /
RESET
NEXT
+
OFF
OFF
Clear Mem
Clear Entry
BATTERY
2
3
4
5
6
ON
OFF
2
3
4
5
6
Load
Load
1
2
Spare
Plastic
Insulator

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents