INSTALLATION, SERVICE AND REMOVAL MUST BE BY AN AUTHORISED PERSON ONLY.
AS/NZS 5601 was current at the time of printing but may have been superseded. It is the Installer's
NOTE
responsibility to ensure current requirements are met.
Remove transit protection film. Check for damage, if any is found DO NOT install and contact supplier.

MODEL RANGE OVERVIEW

MP2200, MP2250, MP2210, ACMP2 200 either external or internal in NG or LPG
MP3200, MP3250, MP3210, ACMP3 200 either external or internal in NG or LPG
MP4200, MP4250, MP4210, ACMP4 200 either external or internal in NG or LPG
MP5200, MP5250, MP5210, ACMP5 200 either external or internal in NG or LPG
MP6200, MP6250, MP6210, ACMP6 200 either external or internal in NG or LPG
Rinnai Commercial Manifold Pack hot water systems must only be installed, commissioned, service and removed
by an authorised person in accordance with these instructions, AS/NZS 5601, AS/NZS 3000, AS/NZS 3500 and
local regulations and municipal building codes including local OH&S requirements.
Rinnai Manifold Pack hot water systems are not suitable or approved as a pool heater.
Read these instructions carefully before proceeding with the installation.

LOCATION

Ensure reasonable access for installation, servicing and removal. All valves, controls and pumps etc must be
easily accessible.
When using free standing frames the system must be mounted on a solid level base, capable of supporting the
weight of the appliance when full of water. Ensure components are not allowed to stand in water.
Manifold Pack can be plumbed "left handed", "right handed" or "equal flow" as staging determines operating
sequence of heaters, not the plumbing. Stage-less or larger systems may need to be "equal flow", contact Rinnai
Commercial for assistance.
Gas booster flue terminals must be located in accordance with AS/NZS 5601 Fig 6.2 "Location of balanced flue
terminals".
Rinnai HD units are fan assisted appliances and thus have lower clearances than a natural draft appliance of the
same MJ rating.
HD200e, HD250e, HD210e (External Models)
This appliance is designed for 'Outdoor' Installation only. As such,it must be located in an above ground open
air situation with natural ventilation, without stagnant areas, where gas leakage and products of combustion are
rapidly dispersed by wind and natural convection.
This appliance must be mounted on a vertical structure with the water and gas connections on the underside
pointing downwards. For appliances installed on elevated structures or under floors specific requirements apply.
Refer to AS/NZS 5601 Section 6 for details.
This appliance must not be used as a domestic spa or swimming pool heater.
Location of the appliance flue terminal must be in accordance with Section 6 and Figure 6.2 of AS/NZS 5601.
Figure 6.2 is reproduced in the 'Horizontal Flue Terminal Clearances' section of these instructions.
Note: that AS/NZS 5601 is current at the time of printing. It is the Installers' responsibility to ensure current
requirements are met.
HD200i, HD210i (Internal Models)
This appliance is designed for 'Indoor' installation only. It may be installed 'Outdoors' in an enclosure if the
requirements of AS/NZS 5601 Section 6 are satisfied. An enclosure is defined as a compartment, enclosed area
of partitioned off space primarily used for the installing of the appliance.
Rinnai
WARNINGS & IMPORTANT INFORMATION
5
Commercial Manifold Pack OIM