This table describes the status LEDs of the safety relay [A61].
CH1
Mode
off
off
green
green
off
flash
green
off
flash
green
green
flash
green
off
blue
off
blue
green
blue
green
blue
green
blue
fast flash
blue
green
fast flash
blue
green
off
flash blue
off
flash blue
green
flash blue
red
fast flash
blue
red
flash red
red
fast flash
red
red
fast flash
red
fast flash
fast flash
red
red
For more information see
Option description and instructions
CH2
Comment
off
The safety relay is not powered.
green
CH1 and CH2 accepted.
Reset done and outputs activated.
off
CH1 and CH2 unaccepted. A timer
function is counting down while the
safety relay remains activated.
green
CH1 unaccepted and CH2 accepted. A
timer function is counting down while
the safety relay remains activated.
off
CH1 accepted and CH2 unaccepted. A
timer function is counting down while
the safety relay remains activated.
off
No channels accepted.
green
CH1 unaccepted, CH2 accepted
off
CH1 accepted, CH2 unaccepted
green
CH1 and CH2 accepted, the safety
relay wait for reset.
fast flash
Two-channels error: CH2 has been
green
unaccepted and then accepted again
while CH1 remained accepted.
green
Two-channels error: CH1 has been
unaccepted and then accepted again
while CH2 remained accepted.
fast flash
Reading error on R1 and R2.
green
off
CH1 and CH2 unaccepted, a timer
function is counting down while
remaining deactivated.
green
CH1 unaccepted and CH2 accepted, a
timer function is counting down while
remaining deactivated.
off
CH1 accepted and CH2 unaccepted, a
timer function is counting down while
remaining deactivated.
red
Failsafe mode, a new setting has
been stored.
red
Failsafe mode, the system is waiting
for a new setting.
red
The safety relay is in failsafe mode.
fast flash
Failsafe mode due to short circuit
red
between CH2 and 24 VDC or T1
red
Failsafe mode due to short circuit
between CH1 and 24 VDC or T2
2TLC010002M0201
3ADW000508R0201+Q964 E-Stop cat.1 without opening mains contactor en b
Action
Check A1–A2 voltage and
connections.
Check CH1 and CH2
Check CH1
Check CH2
Check reset settings, wiring
and reset circuit.
Check installation. Restore
by opening and closing
both CH:s at the same time.
Check installation. Restore
by opening and closing
both CH:s at the same time.
Check installation. Restore
by opening and closing
both CH:s at the same time.
Power cycle the unit to use
the stored setting.
Enter and store a new
setting.
Check error codes and
installation.
Check error code.
Check and remove the short
circuit.
Check error code.
Check and remove the short
circuit.