Mitsubishi Electric MUZ-FS06NA Service Manual page 54

Outdoor unit
Hide thumbs Also See for MUZ-FS06NA:
Table of Contents

Advertisement

OPERATING PROCEDURE
5. Removing the compressor and 4-way valve
(1) Remove the top panel, cabinet and service panel. (Refer to
section 1.)
(2) Remove the back panel. (Refer to section 1.)
(3) Remove the inverter assembly. (Refer to section 2.)
(4) Recover gas from the refrigerant circuit.
NOTE: Recover gas from the pipes until the pressure gauge
shows 0 PSIG.
(5) Detach the brazed part of the suction and the discharge pipe
connected with compressor.
(6) Remove the compressor nuts.
(7) Remove the compressor.
(8) Detach the brazed parts of 4-way valve and pipe. (Photo 13)
© Copyright 2020 MITSUBISHI ELECTRIC CORPORATION
Published: Nov. 2020. No. OBH873
Made in Japan
HEAD OFFICE: TOKYO BUILDING, 2-7-3, MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN
PHOTOS/FIGURES
Photo 12
Brazed part of
the discharge pipe
Discharge temperature thermistor
Photo 13
Specifications are subject to change without notice.
54
Brazed part of
the suction pipe
Brazed parts of
4-way valve