Siemens SIMATIC PCS 7 System Manual page 204

Process control system cpu 410-5h process automation/cpu 410 smart
Hide thumbs Also See for SIMATIC PCS 7:
Table of Contents

Advertisement

Technical data
14.1 Technical specifications of the CPU 410-5H; (6ES7 410-5HX08-0AB0)
Integrated RAM, max.
Expandable RAM
Battery backup
Available
With battery
Without battery
Battery
Backup battery
Backup battery current, typ.
Backup battery current, max.
Backup battery time, max.
Feed of external backup voltage to the CPU
CPU processing times
For bit operations, typ.
For word operations, typ.
For integer math, typ.
For floating-point math, typ.
Processing time (for 1000 binary instructions)
CPU speed
PCS 7 process objects
Average processing time of PCS 7 typicals
Process tasks, max.
CPU blocks
DB
Number, max.
Size, max.
FB
Number, max.
Size, max.
FC
Number, max.
Size, max.
OB
Number, max.
Size, max.
Number of free-cycle OBs
Number of time-of-day interrupt OBs
Number of time-delay interrupt OBs
Number of cyclic interrupt OBs
Number of process interrupt OBs
Number of DPV1 interrupt OBs
Number of restart OBs
204
6ES7410-5HX08-0AB0
48 MB
No
Yes
Yes; all data
No
370 µA; valid to 40 °C
2.1 mA
Covered with the conditions and effects described in the
Module Data manual
No
7.5 ns
7.5 ns
7.5 ns
15 ns
7.5 µs
450 MHz; multiprocessor system
100 ... approx. 2600 can be set with system expansion card
110 µs; with APL typicals
9; can be set individually from 10 ms to 5 s
16000; number range: 1 to 16 000 (= instances)
64 KB
8000; number range: 0 to 7999
64 KB
8000; number range: 0 to 7999
64 KB
See instruction list
64 KB
1; OB 1
8; OB 10-17
4; OB 20-23
9; OB 30-38 (= Process tasks)
8; OB 40-47
3; OB 55-57
2; OB 100, 102
CPU 410-5H Process Automation/CPU 410 SMART
System Manual, 09/2014, A5E32631667-AB

Advertisement

Table of Contents
loading

Table of Contents