Field Configuration

The following configurations must be set in the 09FC controls per
the site application for proper operation.
POINT NAME
Cool Enable
Leaving Water Temp Setpoint
Outdoor Air Temp Setpoint
OAT Offset Setpoint
Remote Contact Normal Logic
State
Fan VFD Run Status Normal Logic
State
Fan VFD Output Type
Fan Initial Start Speed
Fan Minimum Speed
Fan Speed PID
Bypass Valve PID
Lvg Wtr Temp Setpoint OA Reset Enables OA reset of the leaving water temperature's setpoint.
Maximum LWT Setpoint OA Reset The highest leaving water temperature setpoint reset allowed by the outdoor
Table 14 — Field Configuration
DESCRIPTION
Enables or disables cooling operation.
The leaving water temperature setpoint maintained by the module.
The outside air temperature below which the module is allowed to operate.
The number of degrees that the outdoor air temperature must rise above set-
point to disable the module's operation.
Specifies the remote contact's normal logic state.
Specifies the fan's variable frequency drive run status normal logic state.
Defines the type of fan variable frequency drive output control.
The speed that the module's fans are briefly run on initial startup.
The lowest speed that the module's fan is commanded when the fans' vari-
able frequency drive is enabled.
The BACnet Object calculates the amount of fan speed required to satisfy the
Leaving Water Temp Setpoint and allows access to the control loops tuning
parameters.
NOTE: The following default values should be charged only by a technician
trained in tuning PID loop algorithms.
Action
direct
Update Interval
1:00 mm:ss
Proportional
15
Integral
5
Derivative
0
Deadband
0
Bias
0
This BACnet Object calculates the amount of bypass required to satisfy the
Leaving Water Temp Setpoint when bypass valve modulation is enabled and
allows access to the control loop's tuning parameter.
NOTE: The following default values should be changed only by a technician
trained in turning PID Loop algorithms.
Action
reverse
Update Interval
1:00 mm:ss
Proportional
10
Integral
2
Derivative
0
Deadband
0
Bias
0
air temperature.

LEAVING WATER SETPOINT

OUTDOOR AIR SETPOINT

The Table 14 below is a reference for the major points in the con-
trol. For a detailed list see appendix B.
50
DEFAULT/RANGE
D: Enable
R: Disable/Enable
D: 44°F
R: 15 to 75°F
D: 50°F
R: –20 to 80°F
D: 3°F
R: 1 to 10°F
D: Open
R: Open/Closed
D: Open
R: Open/Closed
D: 0-10V
R: 0-10V/2-10V
D: 100%
R: 0 to 100%
D: 20%
R: 0 to 100%
R: 0 to 100%
R: 0 to 100%
D: Disable
R: Disable/Enable
D: 10°F
R: 0 to 25°F