Between Indoor unit and Outdoor unit Connection Cable Specifications(Common in use)
Power supply
Power supply
Max/Min(V)
1Φ, 220-240V, 50Hz
 For Indoor Power Cable, use the grade H07RN-F or H05RN-F materials.
1-phase terminal block spec
AC power : M5 screw
1(L) 2(N)
L
15
12
3-phase terminal block spec
AC power : M4 screw
1(L) 2(N)
L1(R)
L2(S)
9.95
Indoor Power Cable
±10%
CV 1.5mm², 3wires
When installing the indoor unit in a computer room or net work room, use the double
shielded (Tape aluminum / polyester braid + copper ) cable of FROHH2R type.
Communication : M3 screw
N
Communication : M3 screw
L3(T)
N
11.55
Communation Cable
0.75~1.25mm², 2wires
6.7
9.7
6.7
9.7
Home Server
0.75mm², 2wires
11