Hisense AVWT-76FKFSHA Technical Handbook page 524

Vrf air-conditioner (heat recovery)
Hide thumbs Also See for AVWT-76FKFSHA:
Table of Contents

Advertisement

(2) Heat Exchanger Mode Control
In accordance with the connectable indoor unit operation mode, the outdoor unit heat exchanger is switched
as shown in the table below.
Heat Exchanger Mode at Cooling: Condenser COND
Heat Exchanger Mode at Heating: Evaporator EVAP
The Number of Outdoor Unit: 1 (one)
Cooling Mode
Heat Exchanger
Mode
Heat Exchanger
Condition
RVR2
Reversing
Valve
RVR1
EVO
HEX SC
MV5
Expansion
Valve
EVB
Td-SC
NOTE:
1. Heat Exchanger Condition
COND
: Use as Condenser
cond
: Avoid the use of Heat Exchanger (under a high pressure condition)
EVAP
: Use as Evaporator
2. Control Method of Expansion Valve
HEX SC: To adjust to achieve the target value of heat exchanger SC
HEX SH: To adjust to achieve the target value of heat exchanger SH
Pd: To adjust to achieve the target value of Discharge Pressure
Tf: To adjusted to suppress Inverter Temperature increase
Td-SC: To adjusted to achieve the target value of compressor discharge temperature and SC
of liquid refrigerant
3. COND, D1, D1-1, D4 and EVAP are the reference numbers.
Mainly Cooling Mode
COND
D1
COND
COND
OFF
OFF
ON
OFF
HEX SC-Pd
Tf
Tf
Td-SC
Mainly Heating Mode
D1-1
cond
OFF
OFF
HEX SC-Pd
Tf
Td-SC
517
PRODUCT SPECIFICATION
Heating Mode
D4
EVAP
EVAP
EVAP
ON
ON
OFF
OFF
HEX SH
HEX SH
Tf
Tf
Td-SC
Td-SC

Hide quick links: