2.7: Troubleshooting Guidelines in fault condition when

motor stops while it is in running condition

Table: 14 FASD starter operating sequence in fault condition
6A
6B
6C
Motor
LMR
Amber
conditon
Mode
LED
Not
Manual
Blink
Running
Not
Auto
Blink
Running
Not
Bypass
Blink
Running
#: Phase loss
, Phase reversal
1
NA – Starter is unprotected from incoming power supply faults,only protection from load side faults. In this mode, amber LED
will continously ON if incoming power supply is healthy and will blink if the incoming power supply is unhealthy– Refer 2.8
Starter Fault conditon:
1) LMR-A: Manual mode
6A
: Motor suddenly stops after running for some time.
6B
: Check the mode of LMR-A, if it is Manual mode.
6C
: Amber LED will start blinking
6D, 6E
: Follow steps from 5G to 5H of manual mode (Refer Table no.12; Corrective action 1)
6F to 6L : Follow steps from 4B to 4I of manual mode (Refer Table no.11)
6M
: Motor starts running again.
2) LMR-A: Auto mode
6A
: Motor suddenly stops after running for some time.
6B
: Check the mode of LMR-A, if it is Auto mode.
6C
: Amber LED will start blinking
6D, 6E
: Follow steps from 5G to 5H of Auto mode (Refer Table no.12; Corrective action 2)
6F to 6L : Follow steps from 4B to 4I of Auto mode (Refer Table no.11)
6M
: Motor starts running again
3) LMR-A: Bypass mode
As in Bypass mode there is no protection from the inconing supply faults, however there may some conditions,
example mentioned below where Starter may not ON –
1. Phase loss
2. Incmoing supply voltage less than the minimum required operational voltage of the Starter.
3. Incoming supply voltage is very high
etc.......
In the above conditions check the Starters as explained in Auto & Manual Mode.
6D
6E
6F
Possible
Corrective
3 main
causes
action
supply
of fault
#
1)
ON
#
2)
ON
NA
NA
ON
, Under voltage
, Over voltage
2
3
6G
6H
Amber
On-
Amber
LED
Delay
Blink
(On-delay
0.5-5min
duration)
Blink
0.5-5min
(On-delay
duration)
Blink
0.5-5min
(On-delay
duration)
, Phase unbalance
4
5
6I
6J
6K
'ON'
Starter
Green
LED
Push
operation
button
ON
ON
ON
ON
NA
ON
ON
ON
ON
6L
6M
Motor
LED
conditon
ON
Running
ON
Running
ON
Running
22