Demand value measured variables with Modbus function code 0x14

The measured variables listed below can be read out via Modbus function code 0x14 "Read
File Record" in two stages.
● Stage 1 (File Number 1), preset to 10 s
● Stage 2 (File Number 2), preset to 15 min
File
Offset
(FC0x14)
Address
1
1
1
3
1
5
1
7
1
9
1
11
1
13
1
15
1
17
1
19
1
21
1
23
1
25
1
27
1
29
1
31
1
33
1
35
1
37
1
39
1
41
1
43
1
45
1
47
1
49
1
51
1
53
1
55
1
57
1
59
1
61
1
63
1
65
140
Address
Length
FC 0x03
FC 0x04
30001
2
30003
2
30005
2
30007
2
30009
2
30011
2
30013
2
30015
2
30017
2
30019
2
30021
2
30023
2
30025
2
30027
2
30029
2
30031
2
30033
2
30035
2
30037
2
30039
2
30041
2
30043
2
30045
2
30047
2
30049
2
30051
2
30053
2
30055
2
30057
2
30059
2
30061
2
30063
2
30065
2
Name
Time stamp aggregation stage n
Flags aggregation stage n
V_L1
V_L2
V_L3
V_L12
V_L23
V_L31
I_L1
I_L2
I_L3
VA_L1
VA_L2
VA_L3
P_L1
P_L2
P_L3
VARQ1_L1
VARQ1_L2
VARQ1_L3
PF_L1
PF_L2
PF_L3
THDV_L1
THDV_L2
THDV_L3
THDI_L1
THDI_L2
THDI_L3
FREQ
V_LN_AVG
V_LL_AVG
I_AVG
Equipment Manual, 10/2019, L1V30425208F-01
Format
Access
UNIX_TS
R
Uint32
R
Float
R
Float
R
Float
R
Float
R
Float
R
Float
R
Float
R
Float
R
Float
R
Float
R
Float
R
Float
R
Float
R
Float
R
Float
R
Float
R
Float
R
Float
R
Float
R
Float
R
Float
R
Float
R
Float
R
Float
R
Float
R
Float
R
Float
R
Float
R
Float
R
Float
R
Float
R
PAC3120 and PAC3220