◆ Address setting procedure 1
1
Energize indoor units fi rst, and then energize outdoor units.
2
About one minute after energizing the outdoor units, confi rm that the 7-segment display on the
interface P.C. board of the header outdoor unit indicates
3
Press SW 15 to start the automatic address setting.
It normally takes 5 minutes, but may takes as long as 10 minutes to complete the auto address setting for 1
refrigerant line.
4
The 7 segment display will indicate
When the address sequence has covered all the fan coils for a refrigerant line auto - the 7
segment display will indicate
U. 1.
When the fl ashing stops and the display indicates
complete.
Interface P.C. board on the header outdoor unit
SW04
SW05
SW15
3
D600 D601 D602 D603 D604
2,4
SW01
SW02
SW03
REQUIREMENT
• When 2 or more refrigerant lines are controlled as a group (using, 1 remote control), be sure to turn on all the
indoor units in the group before setting the addresses.
(Note: the group control of more than two refrigerant systems is possible only when all the FS units are single
port type.)
• If the unit address of each refrigerant line is set separately, then the header unit for each line will be set
separately. In this case the remote control will display CODE No. "L03" indicating "indoor header unit overlap"
when the system starts running. When this happens the group address must be changed to make only one unit
the header unit. This operation is done using the wired remote control.
(Example)
Controlling 2 or more refrigerant lines as a group
Outdoor
System wiring
Indoor
Indoor
diagram
Remote
control
39-EN
1122001201_EN FR.indd 20
1122001201_EN FR.indd 20
U. 1. L08
. The U.1. will be fl ashing.
Auto 1 → Auto 2 → Auto 3
.
fl ashing.
U. 1.
without fl ashing, the address setting is
Outdoor
Indoor
Indoor
(Group control)
◆ Address setting procedure 2
1
Set a system address for each system using SW 13 and 14 on the interface P.C. board for the
header outdoor unit of each system.
(Factory default: Address 1)
NOTE
Set a unique address for each system. Do not reuse any address from another system (refrigerant line).
Interface P.C. board on the header outdoor unit
SW06
SW07
SW09
1 2 3 4
1 2 3 4
1 2 3 4
SW11
SW12
SW13
1 2 3 4
1 2 3 4
1 2 3 4
Switch settings for a line (system) address on the interface P.C. board for the outdoor unit
(✕: switch OFF)
SW13
Line (system) address
4
1
1
2
ON
3
4
ON
5
6
ON
7
8
ON
9
10
ON
11
12
ON
13
14
ON
15
16
ON
17
ON
18
ON
ON
19
ON
20
ON
ON
21
ON
22
ON
ON
23
ON
24
ON
ON
25
ON
26
ON
ON
27
ON
28
ON
ON
– 20 –
SW10
1 2 3 4
SW14
1 2 3 4
SW14
2
3
4
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
EN
FR
40-EN
9/2/16 1:30 PM
9/2/16 1:30 PM

Advertisement

Table of Contents
loading

Table of Contents