GENERAL
M300CJ Control Module
able Control Module provides Johnson Controls intelligent
control panels a circuit for Notification Appliances (horns,
strobes, speakers, etc.) or to monitor a telephone circuit.
Addressability allows the M300CJ to be activated, either
manually or through panel programming, on a select (zone
or area of coverage) basis.
M300RJ Relay Module
Relay Module provides the system with a dry-contact output
for activating a variety of auxiliary devices, such as fans,
dampers, control equipment, etc. Addressability allows the
dry contact to be activated, either manually or through panel
programming, on a select basis.
FlashScan®
(U.S. Patent 5,539,389) is a new communi-
cation protocol developed by NOTIFIER Engineering that
greatly enhances the speed of communication between ana-
log intelligent devices. Intelligent devices communicate in a
grouped fashion. If one of the devices within the group has
new information, the panel CPU stops the group poll and
concentrates on single points. The net effect is response
speed greater than five times that of other designs.
FEATURES
• Built-in type identification automatically identifies these
devices to the control panel.
• Internal circuitry and relay powered directly by two-wire SLC
loop. The M300CJ module requires power (for horns, strobes,
etc.), audio (for speakers), or a telephone riser (for hand-
sets). Internal relay feature available on FlashScan® systems
only.
• Integral LED "blinks" green each time a communication is
received from the control panel and turns on in steady red
when activated.
• LED blink may be deselected globally (affects all devices).
• High noise immunity (EMF/RFI).
• The M300CJ may be used to switch 24-volt NAC power,
audio (up to 70.7 V
) or telephone.
RMS
• Wide viewing angle of LED.
• SEMS screws with clamping plates for wiring ease.
• Direct-dial entry of address 01 – 159 on FlashScan® sys-
tems (IFC-640, IFC-3030), or 01 – 99 on traditional systems
(IFC-400, IFC-640, IFC-1010/2020, IFC-3030, or FC-2000).
• Speaker, audible/visual, and telephone applications may
be wired for Class B or A (Style Y or Z).
APPLICATIONS
The M300CJ is used to switch 24 VDC audible/visual power,
high-level audio (speakers), or control telephone devices. The
M300RJ may be programmed to operate dry contacts for door
holders, Air Handling Unit shutdown, etc., and to reset four-
wire smoke detector power.
This document is not intended to be used for installation purposes. We try to keep our
product information up-to-date and accurate. We cannot cover all specific applications
or anticipate all requirements. All specifications are subject to change without notice.
— The M300CJ Address-
— The M300RJ Addressable
For more information, contact your
Johnson Controls Field Support Center.
507 East Michigan Street, Milwaukee, WI 53202
May 24, 2004
M300CJ
and
Control and Relay Modules
with FlashScan®
MEA
457-99-E
Vol. VIII
S1570
MARYLAND
State Fire Marshal
Permit #2029
M300CJ Module
(See wiring diagram Fig. 5 for M300RJ)
CONSTRUCTION
• The face plate is made of off-white Noryl®.
• Controls include two rotary switches for direct-dial entry of
address (01-159).
• The M300CJ is configured for a single Class B (Style Y) or
Class A (Style Z) Notification Appliance Circuit.
• The M300RJ provides two Form-C dry contacts that switch
together.
OPERATION
Each M300CJ or M300RJ uses one of 159 possible module
addresses on a SLC loop. It responds to regular polls from
the control panel and reports its type and status, including
the open/normal/short status of its Notification Appliance
FlashScan® is a registered trademark of NOTIFIER. Noryl® is a
registered trademark of GE Plastics, a subsidiary of General Elec-
tric Company.
JCI-6724
M300RJ
California
State Fire
Marshal
7300-0554:131
JCI-6724 • 05/24/04 — Page 1 of 4

Advertisement

loading

Summary of Contents for Johnson Controls M300CJ

  • Page 1 ) or telephone. address (01-159). • Wide viewing angle of LED. • The M300CJ is configured for a single Class B (Style Y) or • SEMS screws with clamping plates for wiring ease. Class A (Style Z) Notification Appliance Circuit.
  • Page 2 Upon code command from the panel, the M300CJ will dis- i t s connect the supervision and connect the external power sup- ply in the proper polarity across the load device. The discon-...
  • Page 3 5) M300RJ: Relay module wiring diagram. Fig. 1 M300CJ: Typical notification appliance circuit configuration, NFPA Style Y. • Connect modules to Listed compatible Johnson Controls control panels only. • All wiring shown is supervised and power limited. • Module polarities are shown in alarm.
  • Page 4 • Module polarities are shown in alarm. 6724wir3.wmf Fig. 4 M300CJ: Typical fault-tolerant wiring for speaker supervision and switching, NFPA Style Z. • Connect modules to Listed compatible Johnson Controls control panels only. • All wiring shown is supervised. • Wires must be supervised per NFPA.