Connect The Controller To The Boiler With A; Rt Terminal - Vaillant VRT 350 Installation Instructions Manual

Table of Contents

Advertisement

7.
Connect the eBUS line to the terminal block of the boiler
(2).
5.2

Connect the controller to the boiler with a

"24V=RT terminal"
1.
Disconnect the power supply to the boiler.
2.
Disconnect the boiler from the power mains by pulling
out the mains plug or de-energising the boiler using a
partition with a contact opening of at least 3 mm.
3.
Secure the power supply to the boiler against being
switched on again.
4.
Check that there is no voltage in the boiler.
0020131957_01 VRT 350 Installation instructions
Electrical installation 5
1
2
Burner
off
1
Controller terminal block
5.
Check whether the bridge is installed between the 24
V=RT terminals on the PCB of the electronics box and,
if required, install the bridge between the 24 V=RT ter-
minals.
2
Boiler terminal block
11