2-24. E: 74. Outdoor temperature thermistor error (Outdoor unit)
Wired remote
Indicator
controller
Outdoor unit main PCB
Detective actuator
Outdoor temperature thermistor
Forecast of cause
Check point 1. Check connection of connector
•
Check if connector is loose or removed.
•
Check erroneous connection.
•
Check if thermistor cable is open
-> Reset power when reinstalling due to removed connector or incorrect wiring.
Check point 2. Remove connector and check thermistor resistance value
•
For the outdoor temperature thermistor resistance value, refer to
sistance values"
•
If thermistor is either open or shorted, replace it and reset the power.
Check point 3. Check voltage of main PCB
Make sure circuit diagram of outdoor unit and check terminal voltage at thermistor
(DC 5.0 V).
NOTE: For details of thermistor connector, refer to "Wiring diagrams" in Chapter 2.
TECHNICAL DATA AND PARTS LIST.
If the voltage does not appear, replace main PCB.
2-24. E: 74. Outdoor temperature thermistor error (Outdoor unit)
Error code
↓
on page 03-61.
↓
↓
End
When outdoor temperature thermistor open or short
circuit is detected at power on or while running the
compressor
Connector failure
Thermistor failure
Main PCB failure
"Thermistor re-
- (03-29) -
E: 74
2. Troubleshooting with error code