Panasonic S-100PK1E5A Technical Data & Service Manual page 31

Hide thumbs Also See for S-100PK1E5A:
Table of Contents

Advertisement

Automatic Address Setting
Basic wiring diagram
Link wiring
NOTE
A terminal plug (black) is attached to each of the outdoor unit control PCBs.
At only one outdoor unit, leave the terminal plug shortcircuit socket on the "Yes" side.
At all the other outdoor units, change the socket (from "Yes" to "No").
A maximum of 8 indoor units can be connected to 1 remote controller for group control.
Refrigerant
system No. 1
System address
rotary switch on
(Change setting to "1")
the outdoor unit
PCB
Outdoor unit
Terminal board 1, 2
Terminal board 1, 2
Indoor unit
Remote controller
Automatic address setting from the outdoor unit (Type U1, T2, F1, N1 and Y2)
Case 1
If the power can be turned ON separately for the indoor and outdoor units in each system:
The indoor unit addresses can be set without running the compressor.
Be sure to use a jig for short-circuiting.
(1) Turn on the indoor and outdoor unit power for refrigerant system 1.
Short-circuit the AUTO ADD (CN041) pin.
Communication for automatic address setting begins.
LED 1 and 2 on the outdoor unit control PCB blink alternately, and turn OFF when address setting is completed.
(2) Next, turn ON the power only at the indoor and outdoor units in a different system. Short-circuit the AUTO ADD
(CN041) pin.
LED 1 and 2 on the outdoor unit control PCB blink alternately, and turn OFF when address setting is completed.
Repeat the same procedure for each system and complete automatic address setting.
(3) Operation using the remote controller is now possible.
No. 1
Inter-unit
control
wiring
1-1
1-2
Remote control communication
wiring for group control
<Approximately 4 – 5 minutes are required.>
Refrigerant
system No. 2
(Change setting to "2")
Change the
terminal
No. 2
plug (black)
short-circuit
socket
2-1
2-2
Remote controller
1-311
Refrigerant
system No. 3
(Change setting to "3")
Change the
terminal plug
(black) short-circuit
No. 3
socket
Inter-unit control
wiring
3-2
3-1
Remote controller
1

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

U-100pe1e5aU-100pe1e8a

Table of Contents