Troubleshooting And Analysis Of Service Problems - Bradford White 500-1825 Installation And Operation Instructions Manual

Volume water heaters
Table of Contents

Advertisement

Internet Version for Reference Only
B4 Volume Water Heater
Black carbon or green soot on a dirty heat
exchanger can, under certain conditions, be
ignited by a random spark or open flame. To
prevent this unlikely occurrence, dampen the
soot deposits with wet brush or fine water
spray before servicing or cleaning the heat
exchanger.
With a wire brush, remove soot and loose scale
from heat exchanger. Clean fallen debris from
bottom of heater. Make sure burner ports are
clear and pilot assembly is free of debris.
d.
Reassemble in reverse order: Be sure the
heat exchanger baffles are replaced.
8.
The gas and electric controls installed on heaters
are engineered for both dependable operation
and long life, but the safety of this equipment
completely depends on their proper functioning.
It is strongly recommended that the basic items
be checked by a competent serviceman every
year and replaced when necessary. The basic
controls are:
a.
Water temperature controls.
b.
Pilot safety system.
c.
Automatic electric gas valve(s).
d.
Flow sensing safety device.
9.
Low water cutoffs should be inspected every six
(6) months, including flushing of float types.
NOTE: Warranty does not cover any damage
caused by lack of required maintenance or improper
operating practices.
10. Both modulating and stage valve are adjusted at
the factory for minimum permissible rates and
should not be readjusted.
SECTION 5.
Troubleshooting and Analysis of
Service Problems
1.
For proper service and problem diagnosis of the
heater and heater system, the following tools are
required:
a.
Gas pressure test kit with range from zero
to 14 W.C. Either a slack tub manometer or
an accurate gas pressure gauge is acceptable
with proper adapters which will connect to
the available fittings in the line and on the
gas valve.
b.
Multi-meter with the following ranges:
0 to 500 volts A.C.
0 to 1000 ohms continuity.
Caution
c.
Tube cleaning kit consisting of reamer,
stainless steel brush, speed handle and
handle extensions.
d.
Heater thermometer (with 1/2" NPT well)
100-240°F.
2.
In addition, the heater should be equipped with
a system pressure gauge with proper ranges for
heater operation.
I. HEATER WILL NOT FIRE.
Possible Cause
A. Electric power is off
B. Operating or safety control
has opened circuit to electric
gas valve.
C. Pilot flame is out.
D. Manual reset device has
tripped.
E. No gas pressure to burners.
F. Electric gas valve operator is
burned out or shortened.
Page 17
What To Do
A. Check to see that main power
switch is "ON." Use testing
device to trace power to
heater junction box.
B. Turn off power. Use continuity
across terminals of each
operating and safety control
switch up to the electric gas
valve. Replace effective
control.
C. Relight pilot per instruction.
D. Follow instructions for start-
up. Reset Pilot safety and all
manual reset safety switches
and reset manual safety gas
valve.
E. Trace gas line to service
shutoff cock. If service cock is
open, trace gas line to meter.
If no pressure is present at
meter, call for public utility
service. If gas is present in
heater inlet, check pressures
in following sequence:
(1) downstream from pressure
regulator. (2) downstream
from electric gas valve.
Replace or adjust as
necessary.
F. Disconnect wiring harness at
gas valve terminals. Check
continuity to actuator coil. If
open circuit or short is