Temperature Sensor

Interconnect the remote temperature sensor by
connecting the temperature sensor to pins 4 and 5 of
TB2. The Remote Temperature Sensor will adjust the
air density value in the controller based on the sensor
measurement when Temperature Compensation is set
to 'Yes'. This density compensation will affect the flow
rate accordingly. If Temperature Compensation is set to
'No', the air density value will be a function of standard
air (70°F/21°C).
®
Specifications
Service: Air and non-combustible,
Enclosure Rating: NEMA-4 and IP56
Dimensions: 5 x 5-3/8 x 2-1/2 inches
Mounting: Mount unit in vertical plane
Accuracy: ±0.5% full pressure scale at
Thermal Effects: 0.015% / °F (0.027% / °C) from
Stability: < ±1% per year
Max. Pressure Limit: 72 psi (1993 inches W.C.)
Temperature Limits: 32° to 140°F (0 to 60°C)
Power Requirements: 24 Vdc or 24 Vac input voltage
Power Consumption: Power = 6VA
Output Signal: User selectable. 4-20 mA (900
Connections: Euro-type removable terminal
Pressure Connections: 1/4 inch quick connect
Weight: 1.5 lbs.
Agency Approvals: ETL #3192905
Sure-Aire™ Flow Monitoring System
compatible gases
(127 x 136.5 x 63.5 mm)
with #8-32 screws
(4 hole locations)
77°F (25°C)
-13° thru 185°F (25° thru 85°C)
ohms max.) or 2-10 Vdc
blocks with 1/2 inch watertight
conduit fittings.