Dimensional Data - York LX Series Installation Manual

Geothermal heat pumps dual capacity
Hide thumbs Also See for LX Series:
Table of Contents

Advertisement

Vertical Dimensional Data
2 ft [61 cm]
Primary Service Access
2 ft [61 cm] Alternate
Service Access. Right Return
Opposite Side
LEFT RETURN
C
Overall Cabinet
Vertical
Top Flow
A
B
C
Model
Width Depth Height
in.
22.5
26.5
39.4
024
cm.
57.2
67.3
100.1
in.
22.5
26.5
44.5
036
cm.
57.2
67.3
113.0
in.
25.6
31.6
50.4
048-
060
cm.
65.0
80.3
128.0
in.
25.6
31.6
54.4
072
cm.
65.0
80.3
138.2
Condensate is 3/4" PVC female glue socket and is switchable from side to front
Unit shipped with 1" [25.4mm] return duct flanges and are suitable for duct connection.
Discharge flange is field installed and extends 1" [25.4mm] from cabinet
Water connections extend 1.2" [30.5mm] beyond front of cabinet.
The optional 1" filter rack (not shown) has the same return opening connection size as the duct flanges shown in the drawing. The filter rack extends 2.25"(57.1 mm)
from the unit.
The optional 1" filter rack is suitable for duct connection.
The optional filter rails (not shown) extend 1.25" (31.75 mm) from cabinet.
3 SERIES VERTICAL SUBMITTAL DATA
TOP
Q
L
R
N
T
S
1.90 4.8
K
J
B
Water Connections
Loop
D
E
F
G
H
Water
Loop
Loop
HWG
HWG
Cond-
FPT
In
Out
In
Out
ensate
2.3
5.3
13.4 16.4
9.6
Swivel
5.8
13.5 34.0 41.7
24.4
2.0
7.0
13.5 16.5
10.2
Swivel
5.1
17.8 34.3 41.9
25.9
2.3
7.3
15.9 18.9
10.6
Swivel
5.8
18.5 40.4 48.0
26.9
2.3
7.3
15.9 18.9
10.6
Swivel
5.8
18.5 40.4 48.0
26.9
P
L
O
M
N
1.90 4.8
H
I
E
D
A
FRONT
Electrical
Connections
I
J
K
3/4"
1/2"
1/2"
HWG
cond
cond
cond
Sweat
Power
Ext
Low
(I.D.)
Supply
Pump
Votage
8.9
11.4
13.7
1"
1/2"
female
22.6
29.0
34.8
9.5
12.1
14.3
1"
1/2"
female
24.1
30.7
36.3
9.8
12.3
14.6
1"
1/2"
female
24.9
31.2
37.1
9.8
12.3
14.6
1"
1/2"
female
24.9
31.2
37.1
19
LX SERIES INSTALLATION MANUAL
TOP
O
Q
R
RIGHT RETURN
T
S
G
F
Discharge Connection
Duct Flange Installed
L
M
N
O
P
Supply
Supply
Width
Depth
6.3 0.7
14.0
14.0
2.7 2.3
16.0 1.8
35.6
35.6
6.9 5.8
6.1 0.8
14.0
14.0
4.4 2.4
15.5 2.0
35.6
35.6 11.2 6.1
6.9 1.1
18.0
18.0
3.8 1.7
17.5 2.8
45.7
45.7
9.7 4.3
6.9 1.1
18.0
18.0
3.8 1.7
17.5 2.8
45.7
45.7
9.7 4.3
C
B
Return Connection
Return Duct Flanges
Q
R
S
T
Return
Return
Depth
Height
22.0
18.0
1.8
55.9
45.7
4.6
22.0
22.0
2.0
55.9
55.9
5.1
28.0
26.0
1.7
71.1
66.0
4.3
28.1
30.0
2.2
71.4
76.2
5.6
7/17/14

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ylf024Ylf036Ylf048Ylf060Ylf072

Table of Contents