Smart Manager
3

System specifications

3-1. Specifications of Smart Manager

Part name
Model name
Power supply
Power consumption
Indoor unit
Connectable unit
Energy monitoring
number
interface
Digital Input/Output
interface
Operating temperature / humidity
Dimension
Mass

3-2. Specifications for wiring

Use the following materials to connect signal lines and power lines (procured on site)
No
1
For TCC-LINK
2
3
(220 - 240 VAC)
4
For Digital Input/Output connection
For power supply
5
(Between the power unit and central controller)

3-3. Specifications for computers

The PC to be connected must meet the following system configuration conditions so that the Smart Manager
operates normally.
Operating system
Hardware
Browser
Excel (*)
* When power distribution function is used.
BMS-SM1280HTLE
Use bundled power unit.
Up to 128 units
(Line1: Up to 64 units, Line2: Up to
64 units)
Up to 4 units.
Up to 4 units
0
120(H) x 180(W) x 64(D) mm
0.8 kg
Line
For RS-485
For power
• Microsoft Windows XP
• Microsoft Windows Vista
• Microsoft Windows 7
Screen resolution 1024 × 768 pixels or more
• Firefox 2.0, 3.0, 3.5 or 3.6
• Internet Explorer 7.0 or 8.0
Excel 2003, 2007, 2010
Central Controller
o
o
C to 40
C, 10 to 90 % RH (no condensation)
Type / Wire size / Length
1.25 mm², 1000 m max. (total length including
2.00 mm², 2000 m max. air conditioner area)
1.25 mm², 500 m max. (total length)
H05RN-F or 245IEC57
0.75 mm², 50 m max.
0.3 mm², 100 m max.
0.75 mm², 20 m max.
Engineering Book
Power Unit
220 - 240 VAC, 50/60 Hz
7W
114(H) x 177(W) x 50(D) mm
0.9 kg
2-core shield wire
2-core shield wire
2-core wire
4-core wire
10