The Base Network may contain a combination of up to 92 subnetworks or
nodes, providing Repeaters are used between segments of 32 RS485 drivers.
Universal
LINC485
Repeater
Node 1
Universal
LINC485
Subnetwork
Universal
LINC485
Repeater
Connection
To provide simple connection the Universal LINC485
uses the same connectors as all YORK ISN control-
lers-a removable, 5-screw press-in connector. In
addition to the screw connector, newer ISN controllers
utilize a USB-style connector. This additional connec-
tor provides a simple method for connecting Universal
LINCs to the controller. If within 3 ft. (1 m) of a new-
style controller equipped with a USB-style LINC port,
sufficient power is provided through the LAN connec-
tion. For installations at greater distances and older
controllers, an optional 5 VDC Power Supply is
available.
2
Router
Subnetwork
Each segment may contain up to 32 nodes.
Each subnetwork may contain 3 segments.
Node 30
Universal
LINC485
Node 31
Router
Nodes on the incoming side of a repeater must be lower than the repeater node.
Nodes on the outgoing side of a repeater must be higher than the repeater node.
Subnetwork
Typical LAN Configuration utilizing Universal LINC485
Node 32
Node 61
Universal
LINC485
Node 62
Repeater

Mounting Configurations

The Universal LINC485 provides several mounting
methods for greater installation flexibility. Shipped in
a housing with a DIN rail mounting clip, the unit can
be attached to any open DIN rail space within an
existing controller. If the controller does not use DIN
rail, the Universal LINC can be removed from the
housing and secured inside the controller with small
screws (1/8 in./4 mm or smaller).
If space is unavailable inside the controller enclosure,
a small, auxiliary enclosure is available. The auxiliary
enclosure includes a DIN rail to mount the Universal
LINC and an accompanying 5 VDC Power Supply. (It
also accepts the TDCE controllers.)